beautypg.com

Linearization 39 – West Control Solutions TB 45 Temperature Monitor User Manual

Page 39

background image

Name

Value range Description

ICnf

Blockierung Konfigurationsebene (nur mit BlueControl sichtbar!)

0

Released

1

Blocked

ICal

Block calibration level (only visible with BlueControl

Ò

!)

0

Released

1

Blocked

Dis1

Selection which value should be displayed on display line 1

0

Display value

1

Limit value LC

T.Dis2

Settings for text in display 2 (max. 5 digits)
(only visible with BlueControl

Ò

!)

Linearization Lin

Only visible via BlueControl

®

!

Name

Value range

Description

U.LinT

Temperature unit of the linearization table

0

without unit

1

in Celsius

2

in Fahrenheit

3

in Kelvin

In.1 … In.16

OFF (ab In.3) -1999...9999

Input 1 … input 16

Ou.1 … Ou.16

-999.0 … 9999

Output 1 … output 16

g

Value U.LinT defines the unit of input values specified for linearization of temperature values. Value entry
in Celsius despite display of the measured value in Fahrenheit is possible.

w

Specify the input signals mV, V, mA, % or Ohm dependent on input type.

w

For special thermocouples (S.tYP = 18), specify the input values in V and the output values in the
temperature unit adjusted in U.LinT.

w

For special resistance thermometer (KTY 11-6) (S.tYP = 23), specify the input values in Ohm and
the output value in the temperature unit adjusted in U.LinT .

g

Resetting to factory setting (default)

r chapter 2.4, 6.9 (page 8)

Configuration level

TB 45

Configuration

39