NOSHOK 800 Series Electronic Indicating Pressure Transmitter/Switch User Manual
Page 10
9
Only for the version with analog output!
Select the pressure value of the analog
output at 4mA/0V.
Only for the version with analog output!
Select the pressure value of the analog
output at 20mA/10V.
Select output filters
Range: 0.00...2.00s
Resolution: 0.01s
Grading: Step Size Range
10ms 0.00...0.2s
50ms 0.2 ...1.0s
100ms >1.0s
Authorization for the user.
The user has the permission
YES: To program
NO: To not program
the switching output in the user menu
Save the previous changes.
YES: Save
NO: Not Save
returns to the actual pressure indication afterwards.
Return to the beginning of the set up menu by pressing the button S1.
To exit the menus
1. After the selection, the menu will automatically be closed whether the modified value is stored or not.
2. It is possible to exit the menu anytime by pressing the buttons S1 and S2 simultaneously.
3. If no button is pressed for 30 seconds, the menu will be closed automatically.
Error message
1. Flashing display of the actual pressure: measured pressure outside of range.
2. Flashing of the display during the programming: An invalid value was entered.
Examples: Switching point above/below the adjustment range, reset point above/below the adjustment range,
reset point above the switching point, analog output span is samller than 20% of the adjustment range
filter more than 2s. When this happens, the buttons are locked for 3s and the switch takes over the next possible value.
M a i n P r o g r a m m i n g - C o n t i n u e d
9
8
Select the switching type of the first switching output.
nPn: n-switching
PnP: p-switching
Select the switching function of the first switching output.
hYSt: Hysteresis
GAtE: Gate Function
Select the first reset point.
Select delay time of the first switching output.
Range: 0.00 ... 99.99s
Resolution: 0.01s
Only for the version with two switching points!
Select the second switching point.
Only for the version with two switching points!
Select delay time of the second switching output.
Range: 0.00 ... 99.99s
Resolution: 0.01s
Only for the version with two switching points!
Select the contact function of the second switching output.
ncLs: Normally closed contact
noPn: Normally open contact
Only for the version with two switching points!
Select the switching type of the second switching output.
nPn: n-switching
PnP: p-switching
Only for the version with two switching points!
Select the switching function of the second switching output.
hYSt: Hysteresis
GAtE: Gate function
Only for the version with two switching points!
Select the second reset point.
Only for the version with two switching points!
Select the delay time of the second reset point.
Range: 0.00 ... 99.99s
Resolution: 0.01s
M a i n P r o g r a m m i n g - C o n t i n u e d