NOSHOK 624 Series Pressure Transmitters User Manual
Pressure transmitters, User manual noshok, Non-incendive
model 624 has G1/2B or G1B flush diaphragm
connections. Refer to the catalog for complete
specifications. Do not torque the process connector
with a force greater than 37 foot pounds.
For the 4 mA to 20 mA output version, install
the power supply, transmitter and receiving
instrument in series to form a 2-wire current
loop. The transducer regulates the current in
the loop.
The transmitter is classified for over-voltage
category II and the pollution degree 1. For the
voltage output version, the 3-wire system uses
separate leads for the power supply and output
signal. The 3rd lead is a common minus.
Use a NEC Class 02 power supply, low
voltage and low current maximum 100 VA even
under fault conditions.
Maintenance
NOSHOK series 623 and 624 non-incendive
pressure transmitters require no maintenance.
The are calibrated at the factory using pressure
standards traceable to N.I.S.T. There are no user
available adjustments.
User Manual
NOSHOK
PRESSURE
TRANSMITTERS
Series 623 and 624