KYORITSU 3128 User Manual
Page 16
12
KEW3128
3. Specification
KEW3128
【Volt Meter】
Range
Voltage Test
Measuring Range
DC Voltage
AC Voltage
±30~±600V
30~600V(50/60Hz)
Accuracy
±2%rdg±3dgt
【Frequency】
Range
Voltage Test
Measuring Range
45.0 ~ 65.0Hz
Accuracy
±0.2Hz
【Ammeter】
Measuring Range
0.0nA ~ 2.40mA
(determined by
resistance and voltage
values)
Depending on the
effective range of
insulation resistances
【Capacity Meter】
Range
500V ~ 5000V Range
10000V / 12000V Range
Accuracy
5.0nF ~ 50.0μF
5.0nF ~ 1.0μF
±5%rdg±5dgt
* Measurements of capacitance of 0.5μ or more shouldn’t be repeated at
10000V/ 12000V Ranges in a short time. (Rough guide: 5 times/ hour)
* A message “Noise Error” may be displayed on the LCD and a measurement
may be ceased at 10000/12000V Ranges. In this case, select a lower Voltage
Range and test again.
【Calculated Value】
PI,DAR,DD
Measurement Mode
PI
DAR
DD
Display Range
0.00 ~ 999
0.00 ~ 999
0.00 ~ 999
Computational error
±2dgt
±2dgt
±2dgt
●
Electromagnetic compatibility (IEC61000-4-3)
Radio-frequency electromagnetic field
= 10V/m : 20times of the specified accuracy