10.2 Proof test report form (for copying)
For more data, refer to
Proof tests
on page 20.
CAUTION!
Complete the report form that follows when you do a proof test.
Recorded by:
Date:
Unique device ID (e.g. serial number):
Parameter value check
Proof tests results
Recorded value
Correct value
Approved
2.3.1 TANK HEIGHT
Correct tank height
[Yes]
[No]
2.4.3 SCALE 4mA
4.000 mA ± 1 μA
[Yes]
[No]
2.4.4 SCALE 20mA
20.000 mA ± 1 μA
[Yes]
[No]
2.4.2 RANGE I
Error value= 3.6 mA
1
[Yes]
[No]
2.6.1 HART ADDRESS
HART address= 0
2
[Yes]
[No]
1 The error value is correct if the menu item is set to "4-20/3.6E" or "3.8-20.5/3.6E"
2 Multidrop is not permitted for SIL-approved devices
Functional check
Proof tests results
Recorded value
Correct value
Approved
Error alarm signal < 3.6 mA
< 3.6 mA
[Yes]
[No]
Current output= 4 mA
1
4 mA ± 400 μA
[Yes]
[No]
Current output= 12 mA
2
12.000 mA ± 400 μA
[Yes]
[No]
Current output= 20 mA
3
20.000 mA ± 400 μA
[Yes]
[No]
1 The tank is full when menu item 2.4.1 OUTPUT FUNC.= Distance. The tank is empty when menu item 2.4.1 OUTPUT
FUNC.= Level.
2 The tank is 50% full.
3 The tank is full when menu item 2.4.1 OUTPUT FUNC.= Level. The tank is empty when menu item 2.4.1 OUTPUT FUNC.=
Distance.
Conclusion
Does the device operate satisfactorily in safety-related systems?
[Yes]
[No]
Signature: