Appendix, 2 proof test report form (for copying) – KROHNE OPTIWAVE 5200C SIL User Manual

Page 33

background image

APPENDIX

10

33

OPTIWAVE 5200 C

www.krohne.com

02/2013 - 4001906202 - AD SIL OPTIWAVE 5200 R02 en

10.2 Proof test report form (for copying)

For more data, refer to

Proof tests

on page 20.

CAUTION!
Complete the report form that follows when you do a proof test.

Recorded by:

Date:

Unique device ID (e.g. serial number):

Parameter value check

Proof tests results

Recorded value

Correct value

Approved

2.3.1 TANK HEIGHT

Correct tank height

[Yes]

[No]

2.4.3 SCALE 4mA

4.000 mA ± 1 μA

[Yes]

[No]

2.4.4 SCALE 20mA

20.000 mA ± 1 μA

[Yes]

[No]

2.4.2 RANGE I

Error value= 3.6 mA

1

[Yes]

[No]

2.6.1 HART ADDRESS

HART address= 0

2

[Yes]

[No]

1 The error value is correct if the menu item is set to "4-20/3.6E" or "3.8-20.5/3.6E"
2 Multidrop is not permitted for SIL-approved devices

Functional check

Proof tests results

Recorded value

Correct value

Approved

Error alarm signal < 3.6 mA

< 3.6 mA

[Yes]

[No]

Current output= 4 mA

1

4 mA ± 400 μA

[Yes]

[No]

Current output= 12 mA

2

12.000 mA ± 400 μA

[Yes]

[No]

Current output= 20 mA

3

20.000 mA ± 400 μA

[Yes]

[No]

1 The tank is full when menu item 2.4.1 OUTPUT FUNC.= Distance. The tank is empty when menu item 2.4.1 OUTPUT

FUNC.= Level.

2 The tank is 50% full.
3 The tank is full when menu item 2.4.1 OUTPUT FUNC.= Level. The tank is empty when menu item 2.4.1 OUTPUT FUNC.=

Distance.

Conclusion

Does the device operate satisfactorily in safety-related systems?

[Yes]

[No]

Signature: