TECHNICAL DATA
9
29
OPTIWAVE 5200 C
www.krohne.com
02/2013 - 4001906202 - AD SIL OPTIWAVE 5200 R02 en
9.3 Characteristics for the device safety function
If it is necessary to use the device in a low demand mode (as specified in document [N2]), refer to
the table below. For example, the device can be used to give a warning if an error signal occurs.
The table shows the change of PFD
AVG
with a T[Proof] between 1 to 10 years:
For more data, refer to
Proof tests
on page 20.
9.4 SIL-specific technical data
Version
Non-Ex / Ex i
Ex d
Firmware version
Converter: 1.00.06; Sensor: 1.00.06
Board version
Converter: 4000678801B;
Sensor: 4001105601B
Converter: 4000678801B;
Sensor: 4001105601B
Ex d barrier: 4000633801A
Systematic capability
2
2
Architecture
1oo1D (daily auto-diagnostic checks)
PFH
9.0Ч10
-8
1.34Ч10
-7
SFF
91.8%
90%
λ
SD
2.1Ч10
-8
9.6Ч10
-8
λ
SU
5.37Ч10
-7
8.37Ч10
-7
λ
DD
5.13Ч10
-7
6.24Ч10
-7
λ
DU
9.0Ч10
-8
1.34Ч10
-7
DC
D
85%
82%
MTBF
97 years
82 years
Year:
1
2
3
4
5
6
7
8
9
10
PFD
AVG
(Non-Ex / Ex i)
3.99
Ч10
-4
7.96
Ч10
-4
1.19
Ч10
-3
1.59
Ч10
-3
1.98
Ч10
-3
2.38
Ч10
-3
2.77
Ч10
-3
3.17
Ч10
-3
3.56
Ч10
-3
3.96
Ч10
-3
PFD
AVG
(Ex d)
5.89
Ч10
-4
1.17
Ч10
-3
1.76
Ч10
-3
2.34
Ч10
-3
2.93
Ч10
-3
3.51
Ч10
-3
4.09
Ч10
-3
4.67
Ч10
-3
5.26
Ч10
-3
5.84
Ч10
-3
INFORMATION!
This data is for SIL-approved devices only. For more data about device characteristics and
performance, refer to
“
Technical data
”
in the technical datasheet, quick start or handbook
(document [N1]).
Measuring system
Measuring principle
2-wire loop-powered level transmitter; X-band (10 GHz) FMCW radar
Application range
Level measurement of liquids, pastes and slurries
Primary measured value
Distance and reflection measurement of 1 product
Secondary measured value
Distance, level, volume, mass and flow rate