beautypg.com

Service, 2 current output check – KROHNE OPTIWAVE 5200C SIL User Manual

Page 24

background image

8

SERVICE

24

OPTIWAVE 5200 C

www.krohne.com

02/2013 - 4001906202 - AD SIL OPTIWAVE 5200 R02 en

8.5.2 Current output check

Do a check of the current output value: 4 mA

• Energize the device.
• Enter the Supervisor menu.
• Push [>>>>], [

] and [>>>>] to go to menu item 2.2.1 SET OUTPUT. Push [>>>>] and then push [

] or [

]

to move up or down the list to set the output to 4 mA.

i

The output will change to the set value after 5 seconds, as an alternative to the measured
value. The current ouput stays at this value while you are in this menu item.

• Measure the current output at the terminals with an ammeter. Does the ammeter show a

current output of 4 mA ± 400 µA?

• Push [^

^

^

^] to go back to the menu list.

i

The current output goes back to the measured value.

• End of the procedure.

Do a check of the current output value: 12 mA

• Push [>>>>] and then push [

] or [

] to move up or down the list in menu item 2.2.1 SET OUTPUT

to set the output to 12 mA.

i

The output will change to the set value after 5 seconds, as an alternative to the measured
value. The current ouput stays at this value while you are in this menu item.

• Measure the current output at the terminals with an ammeter. Does the ammeter show a

current output of 12 mA ± 400 µA?

• Push [^

^

^

^] to go back to the menu list.

i

The current output goes back to the measured value.

• End of the procedure.

Do a check of the current output value: 20 mA

• Push [>>>>] and then push [

] or [

] to move up or down the list in menu item 2.2.1 SET OUTPUT

to set the output to 12 mA.

i

The output will change to the set value after 5 seconds, as an alternative to the measured
value. The current ouput stays at this value while you are in this menu item.

• Measure the current output at the terminals with an ammeter. Does the ammeter show a

current output of 12 mA ± 400 µA?

• Push [^

^

^

^] to go back to the menu list.

i

The current output goes back to the measured value.

• End of the procedure.

CAUTION!
If the values do not agree with the tolerances, then the data supplied by device will not be
correct. For a solution to the problem, speak to the supplier.