7.5 User parameters

7.5.1 Limits for supervisor menu functions related to antenna configuration

INFORMATION!
If you change a parameter set in one or more of the menu items that follow, this will have an
effect on the safety function.

WARNING!
If the device was delivered without an antenna, then calibrate the device to make sure that the
safety function operates correctly. For more data, refer to Calibration procedure on page 23

.

CAUTION!
This section gives data on the modification of a small number of parameters in the 2.0.0
SUPERVISOR menu. If it is necessary to change parameters in the 3.0.0 SERVICE menu or the
4.0.0 MASTER menu, contact your supplier.

If you change the values of one or more of the parameters given in the "User parameters"
section, this can have an unwanted effect on the safety function. Do a check of the safety
function after you change a parameter.

INFORMATION!
Safety function check

Safety function check

Safety function check

Safety function check
Make sure that the 4...20mA measurement range is correctly calibrated.

LEGAL NOTICE!
The manufacturer declines all responsibility for the correct operation of the safety function if
these parameters in the 3.0.0 SERVICE or 4.0.0 MASTER menus are changed by the customer.

Menu

No.

Function

Function description

Selection list

Default value

and comments

2.3.4

STILLWELL EN.

If this menu item is set to "YES",

then you must give the stilling well

height and inner diameter in menu

items 2.3.5 STILLWELL D. and 2.3.6

STILLWELL H..

YES, NO

NO

2.3.5

STILLWELL D.

The inner diameter of the stilling

well. If the device is installed in a

stilling well or has a Wave-Guide

antenna, enter the diameter. The

device will use this data if you set

2.3.4 STILLWELL EN. to "YES". This

menu item is not shown if you set

2.3.4 STILLWELL EN. to "NO".

min-max:

22...999 mm /

0.9...39.3¨

1

2.3.6

STILLWELL H.

The height of the stilling well. If the

device is installed in a stilling well

or has a Wave-Guide antenna,

enter the height. The device will

use this data if you set 2.3.4

STILLWELL EN. to "YES". This

menu item is not shown if you set

2.3.4 STILLWELL EN. to "NO".

min:

500 mm / 19.7¨

max:

2.3.1 TANK HEIGHT

1

2.3.7

ANTENNA.EXT

Optional antenna extensions.These

are attached between the flange

and the antenna.

min:

0 mm / 0¨ or

2.3.6 ANTENNA.EXT

max:

2000 mm / 78.7¨ or

2.3.1 TANK HEIGHT

1