7.4 Error conditions
The device can sense the error conditions in the table that follows. When the device detects a
measurement error, it supplies an output current less than 3.6 mA.
For more data, refer to the "Status and error messages" section in the handbook (document
[N1]).
8
Error mode state
9
Current output (error value)
10
Is the current output setting correct?
10a
No. The current output setting is incorrect.
10b
Yes. The current output setting is correct.
11
Is a new correct measurement available?
11a
No. A correct measurement is not available.
11b
Yes. A correct measurement is available.
1
Initial state (new measurement)
Error condition
Cause
Device does not start
immediately
This error occurs if more than 20 seconds are necessary to start the
device.
The current output is incorrectly
calibrated
Do a current output check. For the procedure, refer to
Current output
check
on page 24. If the values do not agree with the tolerances given
in the procedure, speak to the supplier.
Component hardware errors
Memory failure
Voltage failure
No signal
Microwave failure
Ambient temperature is too high
The ambient temperature is more than +80°C / +176°F.
Ambient temperature is too low
The ambient temperature is less than -40°C / -40°F.
Incorrect measurement signal
(e.g. level lost)
The signal peak is not found within the measuring window that filters
the signals received by the antenna. The measurement is not correct.
Overfill
The level is in the blocking distance. If menu item 2.5.3 OVERFILL EN.
is set to "YES", there is a risk that the product will overflow and cover
the antenna.