TECHNICAL DATA

7

35

OPTITEMP TRA-CXX

www.krohne.com

02/2014 - 4003290501 - MA OPTITEMP TRA-Cxx R01 en

Electrical connections

Power supply

Only necessary when using a temperature transmitter and depends

on transmitter type, typically 24 VDC.

7.5...32VDC for the built-in transmitter.

Power consumption

Only when using a temperature transmitter, typically 550 mW.

Electrical connection

M12-connector (for TRA-C10 and TRA-C30) or Valve EN 175301-803

(for TRA-C20)

Current output

Current output

Current output

Current output

Output range

Exists only when using a temperature transmitter, 4...20 mA

Error signal

Sensor break: Upscale (>=21,0 mA)

Sensor short-circuit: Downscale (<=3,6 mA)

Load

Relevant only when using a temperature transmitter (typically

250 Ω).

Other electrical characteristics

Other electrical characteristics

Other electrical characteristics

Other electrical characteristics

Galvanic isolation

Relevant only when using a temperature external transmitter (see

transmitter handbook).

Time constant

More detailed information can be found in the subsection "Response

times" of the section "Technical data".

Approvals and certificates

Electromagnetic compatibility

For bulit in transmitter EN 61326-1

ESD, Radiated EM-field: Criteria A,

Surge: max 3% of span during disturbance influence

Burst and Conducted RF: max 1% of span during disturbance

influence

For external transmitter, refer to handbook for used temperature

transmitter.

CE

The device fulfils the statutory requirements of the EC directives. The

Manufacturer certifies that these requirements have been met by

applying the CE marking.