TECHNICAL DATA
7
35
OPTITEMP TRA-CXX
www.krohne.com
02/2014 - 4003290501 - MA OPTITEMP TRA-Cxx R01 en
Electrical connections
Power supply
Only necessary when using a temperature transmitter and depends
on transmitter type, typically 24 VDC.
7.5...32VDC for the built-in transmitter.
Power consumption
Only when using a temperature transmitter, typically 550 mW.
Electrical connection
M12-connector (for TRA-C10 and TRA-C30) or Valve EN 175301-803
(for TRA-C20)
Current output
Current output
Current output
Current output
Output range
Exists only when using a temperature transmitter, 4...20 mA
Error signal
Sensor break: Upscale (>=21,0 mA)
Sensor short-circuit: Downscale (<=3,6 mA)
Load
Relevant only when using a temperature transmitter (typically
250 Ω).
Other electrical characteristics
Other electrical characteristics
Other electrical characteristics
Other electrical characteristics
Galvanic isolation
Relevant only when using a temperature external transmitter (see
transmitter handbook).
Time constant
More detailed information can be found in the subsection "Response
times" of the section "Technical data".
Approvals and certificates
Electromagnetic compatibility
For bulit in transmitter EN 61326-1
ESD, Radiated EM-field: Criteria A,
Surge: max 3% of span during disturbance influence
Burst and Conducted RF: max 1% of span during disturbance
influence
For external transmitter, refer to handbook for used temperature
transmitter.
CE
The device fulfils the statutory requirements of the EC directives. The
Manufacturer certifies that these requirements have been met by
applying the CE marking.