ALTOFLUX IFM x080 K-EEx and ALTOFLUX IFM x080 K / i-EEx

12

2

Electrical connection

2.1

Equipotential bonding system

All EEx and EEx/i flowmeters must always be incorporated into the equipotential bonding system
of the hazardous area. This connection can be achieved through the PE/FE conductor connected
to the PE terminal in the terminal compartment (see figure of terminal arrangement below) or
through a separate PE conductor, cross s ectional area at least 4 mm

2

, connected to the external

PE clamp, placed below the converter housing.

2.2

Connecting cables

NOTE:

The below described cables are shown in the following connection diagram .


Cable A:
Signal cable for current output and binary outputs (pulse and status output): The cable parameters
must be in accordance with the regulations in the EN 60079-14 "Electrical installations in
hazardous locations" or an equivalent national standard. For the MODIS version with IFC 090i-
EEx electronics unit (right detail in connection diagram) the signal cable for the intrinsically safe
signal in-/outputs must also conform the requirements as specified in the relevant standard
national code of practice for the installation of electrical apparatus with type of protection Intrinsic
Safety "i".

Cable B:
Power supply cable: The cable parameters must be in accordance with the regulations of the EN
60079-14 "Electrical installations in hazardous locations" or an equivalent national standard.

Rated voltage

500 V

Examples:

H07...-., H05...-.

Equipotential bonding conductor
Cross-sectional area:


4 mm

2

(equivalent to AWG 10)