KROHNE IFC 210 E Short EN User Manual
Page 25
Part B IFC 210 Signal converter Sect. 4.2
05/2002
IFC 210 E 25
Fct.
Display-Texts
Description and settings
Field Frequenz
Set Magnetic field frequency (f
Netz
= power frequency)
•
1
/
2
×
f
Netz
•
1
/
6
×
f
Netz
•
1
/
18
×
f
Netz
•
1
/
36
×
f
Netz
Select with
↑
key.
Press
↵
key to transfer to subfunction “Flow Direction”.
for DC devices to subfunction „Line Frequenz“
Line Frequenz
Normal line frequency in your country
This function is only provided for units with DC power supply
• 50 Hz • 60 Hz
Select with
↑
key.
Press
↵
key to transfer to subfunction “Flow Direction”.
Flow Direction
Define flow direction (in F/R mode: forward flow).
• + Direction
• - Direction
Select with
↑
key.
Press
↵
key to return to Fct. 3.02 “Flowmeter”.
3.03
Zero Point
Zero calibration
• return
(quit function without making change)
• calculate
(calculate new zero value)
Press
↵
key to start, duration approx. 15-90 seconds.
Save new value, select with
↑
key:
• save no
(do not save zero value)
• save yes
(save new zero value)
• change
(change zero value manually)
Press
→
key to transfer to unit selection:
•
m
3
/h • Liter/s • US Gal/min
• any unit, see Fct. 3.05 (factory setting: Liter/h)
Press
→
key to transfer to number setting.
Value may be max. 10% of Q
100%
Press
↵
key to return to Fct. 3.03 “Zero Point”.
3.04
Entrycode
Entry code required to enter setting mode?
• NO (= entry with
→
only)
• YES(= entry with
→
and Code 1:
→
→
→
↵
↵
↵
↑
↑
↑
)
Press
↵
key to return to Fct. 3.04 “Entrycode”.
3.05
User Units
Set any required unit for flowrate and counting
Text Volumen
Set text for required flowrate unit (max. 5 characters)
Factory-set: Liter or MGal .
Characters assignable to each place: • A-Z, a-z, 0-9, or — (= blank character)
Press
↵
key to transfer to subfunction “Factor Volumen”.
Factor Volumen
Set conversion factor (FM) for volume
Factory set 1.00000 for Liter or 2.64172E-4 for US MGal
(exponent notation, here: 1x 10
3
or 2.64172x10
-4
).
Factor FM = volume per 1m
3
.
Setting range • 1.00000 E-9 to 9.99999 E+9 (= 10
-9
to 10
+9
)
Press
↵
key to transfer to subfunction “Text Time”.
Text Time
Set text for required time unit (max. 5 characters)
Factory-set: hr.
Characters assignable to each place: • A-Z, a-z, 0-9, or — (= blank character)
Press
↵
key to transfer to subfunction “Factor Time”.
Factor Time
Set conversion factor (F
T
) for time
Factory-set: 3.60000 E+3 for hour or 8.64000 E+4 for day
(exponent notation, here: 3.6 x10
3
or 8.64 x10
-4
).
Set factor FT in seconds.
Setting range • 1.00000 E-9 to 9.99999 E+9 (= 10
-9
to 10
+9
)
Press
↵
key to return to Fct. 3.05 “User Units”.
3.06 Application
Set
application
conditions
Flow
Set characterization for flow
• Steady
(steady flow, max. 150% of Q
100%
)
• Pulsating
(pulsating flow, up to 1000% of Q
100%
e.g. caused by reciprocating pumps, refer to Sect. 6.4)
Press
↵
key to transfer to subfunction “Empty Pipe”.
Empty Pipe
Signal when measuring tube is empty (refer to Sect. 6.3 )
• no • yes (possible only with built-in option)
Press
↵
key to return to Fct. 3.06 “Application”.