8 IFC

010

Connection of shields to the IFC 010

1 DS Signal cable

2 Shield terminal for shielded signal cable

3 Field power cable

4 Shield terminal for shielded field power cable

5 Housing wall, signal converter

6 Cable

entries

2

Electrical connection

of outputs

2.1 Current output I

• The current output is galvanically isolated from all input and output circuits.

• Typical current output

approx. 15 V DC positive
voltage of current output

current sink




chassis ground, current output

• The current output can also be used as an internal voltage source for the outputs.

U

int

= 15 V DC

I = 23 mA when operated without receiver instruments at the current output

I = 3 mA when operated with receiver instruments at the current output

• Connection diagrams, see Sect. 2.3.

2.2 Pulse output P and status
output S

• The pulse and status outputs are galvanically isolated from the current output and all input circuits.

• Typical pulse and status outputs B1

S status

output

P

⊥ chassis

ground

P pulse

output

• The pulse and status outputs can be operated in the active or passive mode.

Active mode:

The current output is the internal voltage source, connection of electronic totalizers

Passive mode:

External DC or AC voltage source required, connection of electronic or
electromechanical totalizers

Digital pulse division, interpulse period is non-uniform. Therefore, if frequency meters or cycle counters are
connected, allow for minimum counting interval:

10.000

gate time, counter ≤

P

100%

[ Hz ]