Exchange signal conditioning instrument or return it for

repair

3 Should the failure lamp extinguish, you can connect the

sensor again. Separate the signal conditioning instrument

from the connection cable and connect a resistor of 1

kOhm to the sensor input

4 If the failure lamp continues to light, the connection cable is

probably interrupted
Check the connection cable to the sensor

5 Should the failure lamp extinguish, the sensor will be

defective
Exchange sensor or return it for repair

?

The red failure LED of the signal conditioning instrument

lights

l

Current value >22 mA

à

Measure the current value on the signal cable to the

sensor

1 Check all connections and connection cables to the sensor
2 If the red failure lamp continues to light, separate the

sensor from the connection cable and connect a resistor of

1 kOhm instead on the signal conditioning instrument
If the failure lamp extinguishes, the sensor is defective.

Check the connected sensor

3 If the failure lamp continues to light, connect the sensor

again. Separate signal conditioning instrument from the

connection cable and connect a resistor of 1 kOhm to the

sensor input.

4 If the failure lamp extinguishes, this is probably due to a

shortcircuit in the connection cable
Check the connection cable to the sensor

5 If the failure lamp continues to light, the signal conditioning

instrument is defective
Exchange signal conditioning instrument or return it for

repair

22

SU 501 Ex - Signal conditioning instrument

Maintenance and fault rectification