5 Connecting to power supply

5.1 Preparing the connection

Always observe the following safety instructions:

l

Connect only in the complete absence of line voltage

l

If overvoltages are expected, overvoltage arresters should

be installed.

In hazardous areas you should take note of the appropriate

regulations, conformity and type approval certificates of the

sensors and power supply units.

The power supply can be 20 … 250 V AC, 50/60 Hz or

20 … 72 V DC.

Power supply of SU 501 Ex is connected with standard cable

acc. to the national installation standards.
Standard two-wire cable without screening can be used to

connect sensors. If electromagnetic interference is expected,

screened cable must be used.

Connect the cable screen on both ends to ground potential. In

the sensor, the screen must be connected directly to the

internal ground terminal. The ground terminal outside on the

sensor housing must be connected to the potential equalisa-

tion.
If potential equalisation currents are expected, the screen

connection on SU 501 Ex must be made via a ceramic

capacitor (e.g. 1 nF, 1500 V). The low frequency potential

equalisation currents are thus suppressed, but the protective

effect against high frequency interference signals remains.

Take note of the corresponding installation regulations for Ex

applications. In particular, make sure that no potential

equalisation currents flow over the cable screen. In case of

grounding on both sides this can be achieved by the use of a

capacitor or a separate potential equalisation.

5.2 Connection procedure

Move to electrical connection and proceed as follows:
1 Snap the socket without SU 501 Ex onto the carrier rail

Note safety instructions

Take note of safety

instructions for Ex

applications

Select power supply

Select connection cable

Cable screening and groun-

ding

Select connection

cable for Ex applica-

tions

12

SU 501 Ex - Signal conditioning instrument

Connecting to power supply

27953

-EN
-050616