Full signal

Check if all three switching conditions occur in the correct

sequence and the stated duration. If not, there is a fault in the

measuring system (see chapter "Fault rectification").

Note:

Keep in mind that the connected instruments are activated

during the function test. By doing this, you can check the

correct function of the measuring system.

Test procedure

A-mode

B-mode

1 Simulation of a fault signal (approx. 3 s)

Level relay deenergised

Relay control

lamp off

Relay control

lamp off

1 Simulation of a fault signal

Failure lamp

Failure lamp

lights

Failure lamp

lights

2 Simulation an empty signal (approx. 1.5 s)

Level relay energised

Relay control

lamp lights

Relay control

lamp off

2 Simulation of an empty signal

Failure lamp

Failure lamp off

Failure lamp off

3 Simulation of a full signal (approx. 1.5 s)

Level relay deenergised

Relay control

lamp off

Relay control

lamp lights

3 Simulation of a full signal

Failure lamp

Failure lamp off

Failure lamp off

4 Return to the current operating condition (covered/uncovered)

SU 501 Ex - Signal conditioning instrument