7 Maintenance and fault rectification

7.1 Maintenance

When used as directed in normal operation, SU 501 Ex is

completely maintenance-free.

7.2 Fault rectification

SU 501 Ex offers maximum reliability. Nevertheless faults can

occur during operation. These may be caused by the following,

e.g.:

l

Measured value of the sensor not correct

l

Power supply

l

Interference on the cables

The first measures are checking the input and output signal.

The procedure is described as follows. In many cases the

causes can be determined and faults can be rectified.

?

The red failure LED of the signal conditioning instrument

lights

l

Sensor not connected correctly

à

Measure the current value on the signal cable to the

sensor

In Ex systems, make sure that the Ex protection is not

influenced by the measuring instruments used.

à

Faults on the sensor causing a current change below

2 mA or above 23 mA, cause a fault signal on

measuring instruments.

Causes of malfunction

Fault rectification

Failure

20

SU 501 Ex - Signal conditioning instrument

Maintenance and fault rectification