- If the fail safe relay is deenergized, the red failure lamp

will light

l

Yellow

- Relay control lamp

- The yellow relay control lamp reacts depending on the

set mode (A/B)

- In general, the relay control lamp indicates the

activated (energised) condition of the relay

- A dark relay control lamp means that the relay is

deenergised (transistor blocks)

Laterally on top (covered when mounted) there is a DIL switch

block with six switches. The individual switches are assigned

as follows:

l

1 – A/B mode

- A – Max. detection or overfill protection

- B – Min. detection or dry run detection

l

2 – Switch off delay (za)

l

3 – Switch on delay (ze)

l

4 – Integration time 2 s

l

5 – Integration time 6 s

l

6 – Integration time 12 s

With switch 1 you can adjust the mode (A – overfill protection

or B – dry run protection).
With switch 2 and 3 you can adjust the switch off and/or switch

on delay independently.
In the example (see previous illustration), mode A (max.

detection of overfill protection) is selected (switch 1). The

switch on delay is activated (switch 3) and the integration time

is set to 8 seconds (switch 4, 5 and 6).
With switches 4, 5 and 6 you can adjust the integration time.

The times of the activated time switches accumulate. If the

switch on (ze) and switch off delay (za) are switched on

together, the adjusted time applies to both delay modes.

Information:

Keep in mind that the integration time of the sensor and signal

conditioning instrument accumulate.