beautypg.com

KROHNE SU 501 EX EN User Manual

Page 21

background image

+

-

V

mA

12... 20V

4... 20mA

1

2

1

2

3

4

Fig. 8: Connection of a multimeter

1

SU 501 Ex signal conditioning instrument

2

Sensor

l

Sensor not connected correctly

à

Measure the voltage on the connection cable

In Ex systems, make sure that the Ex protection is not

influenced by the measuring instruments used.

à

The terminal voltage of the sensor is at least 12 V in

normal condition

?

The red failure LED of the signal conditioning instrument

lights

l

Current value <2 mA

à

Measure the current value on the signal cable to the

sensor

1 Check all connections and connection cables to the sensor

The voltage should be approx. 17 … 20 V
If the value is below 17 V, probably the signal conditioning

instrument is defective.
Exchange signal conditioning instrument or return it for

repair

2 If the red failure lamp continues to light, separate the

sensor from the connection cable and connect a resistor of

1 kOhm instead on the signal conditioning instrument
The signal conditioning instrument is defective if the failure

lamp continues to light

SU 501 Ex - Signal conditioning instrument

21

Maintenance and fault rectification

27953

-EN

-050616