Technical data – KROHNE OPTIWAVE 7300C Quickstart EN User Manual
Page 28
4
TECHNICAL DATA
28
OPTIWAVE 7300 C
www.krohne.com
03/2014 - 4000050005 - QS OPTIWAVE 7300 R08 en
Flange version
Flange version
Flange version
Flange version
EN 1092-1
DN40...80 in PN40 (Form B1), DN100…200 in PN16 or PN40 (Form B1),
DN40…150 in PN63 or PN100 (Form B1); others on request
Optional flange facing: Forms C, D, E and F
ASME B16.5
1½¨…8¨ in 150 lb RF, 1½¨...6¨ in 300 lb RF, 1½¨...4¨ in 600 lb or 900 lb RF;
1½¨...2¨ in 1500 lb RJ; others on request
Optional flange facing: RJ (Ring Joint)
JIS B2220
40…100A in 10K; others on request
Hygienic
BioControl
®
DN50; Tri-Clamp
®
2¨; DIN 11851 DN50; SMS 51; others on request
Other
Others on request
Electrical connections
Power supply
Terminals output 1
Terminals output 1
Terminals output 1
Terminals output 1 – Non-Ex / Ex i:
Non-Ex / Ex i:
Non-Ex / Ex i:
Non-Ex / Ex i:
14…30 VDC; min./max. value for an output of 22 mA at the terminal
Terminals output 1
Terminals output 1
Terminals output 1
Terminals output 1 – Ex d:
Ex d:
Ex d:
Ex d:
20…36 VDC; min./max. value for an output of 22 mA at the terminal
Terminals output 2
Terminals output 2
Terminals output 2
Terminals output 2 – Non-Ex / Ex i / Ex d
Non-Ex / Ex i / Ex d
Non-Ex / Ex i / Ex d
Non-Ex / Ex i / Ex d
10…30 VDC; min./max. value for an output of 22 mA at the terminal (additional
power supply needed – output only)
Cable entry
M20×1.5; ½ NPT
G ½ (not for FM- and CSA-approved devices. Not for stainless steel housings.)
M25×1.5 (for stainless steel housings only)
Cable gland
Standard: none
Options: M20×1.5 (for non-Ex and Ex -approved devices with M20×1.5 and M25×1.5
cable entries); others are available on request
Cable entry capacity (terminal)
0.5…1.5 mm²
Input and output
Current output
Current output
Current output
Current output
Output signal
(Output 1)
4…20 mA HART
®
or 3.8…20.5 mA acc. to NAMUR NE 43
7
Output signal
(Output 2 - optional)
4…20 mA (no HART
®
signal) or 3.8…20.5 mA acc. to NAMUR NE 43
Resolution
±3 µA
Temperature drift
Typically 50 ppm/K
Error signal
High: 22 mA; Low: 3.6 mA acc. to NAMUR NE 43
Approvals and certification
CE
This device fulfils the statutory requirements of the EC directives. The
manufacturer certifies successful testing of the product by applying the CE mark.
Explosion protection
Explosion protection
Explosion protection
Explosion protection
ATEX
KEMA 04ATEX1218 X
II 1 G, 1/2 G, 2 G Ex ia IIC T6...T3;
II 1 D, 1/2 D, 2 D Ex iaD 20 or Ex iaD 20/21 IP6X T70°C...T95°C;
II 1/2 G, 2 G Ex d[ia] IIC T6...T3;
II 1/2 D, 2 D Ex tD[iaD] A21/20 IP6X T70°C...T95°C;
II 3 G Ex nA II T6…T3 X
IECEx
IECEx KEM 06.0025 X
Ga Ex ia IIC T6…T3; Ex iaD 20 IP6X T70°C…T 95°C;