beautypg.com

Figure 4. dip switch configuration, 2 front panel access, 3 keying – KEPCO HSF 300W Series (no suffix) Operator Manuals User Manual

Page 8: Dip switch configuration, Re 4

background image

6

HSF 300W 050113

• Position 7 of SW1 either enables (default) or disables using the internal power supply

reference voltage to power the DC ON/ALARM indicator. Position 8 of SW2 either dis-

ables (default) or enables using the HSF output voltage to power the DC ON/ALARM

indicator (requires minimums per Table 4 if enabled) (see PAR 3.8).Only one of these

two must be enabled, the other disabled.

• Position 8 of SW1 either disables (default) or enables the visual alarm indication (see

PAR. 3.7.1).

FIGURE 4. DIP SWITCH CONFIGURATION

3.2

FRONT PANEL ACCESS.

The front panel provides a power ON/OFF switch controlling input power and a "VDC ON" indica-

tor which lights green when the unit is operating. If the unit is connected in a parallel configuration,

the indicator lights red if the unit shuts off automatically, or the POWER switch is set to OFF.

CAUTION: DO NOT repeatedly toggle the power ON/OFF switch as this may cause unit to

fault.

NOTE: The ON/OFF switch must be set to OFF before removing unit from rack adapter.

If remote on-off is not enabled (see PAR. 3.5), the OUTPUT RESET button restores output power

in the event that overcurrent or overvoltage protection has tripped, or thermal overload or fan mal-

function has occurred.

If remote voltage control (see PAR. 3.4.2) is not enabled, the front panel Vadj trimmer (see PAR.

3.4.1) provides adjustment of the output voltage within the limits specified in Table 2; test points

are available at the front panel for monitoring the DC output.

Figure 5 shows the location of all operating controls, indicators and test points followed by an

explanation of each.

3.3

KEYING

Keying of the HSF 300W is established at the factory. The output voltage determines which key

pins are installed (see Figure 3, Detail A). When the proper holes in the rack adapter are blocked

by keying screws installed by the user, only a power supply of the correct voltage can be inserted

in the rack adapter slot. Refer to the RA 19-4C Manual for rack adapter keying instructions.

OFF

ON

OFF

ON

ALARM LED DISABLE

DC ON PWR BY REF

-PF

+PF

-RC

+RC

RV

REF

3043278

8

8

8

SW1

SW2

4

6
7

5

2
3

1

4

4

5
6

7

6
7

5

1
2
3

2
3

1

DC ON PWR BY OUTP V

8

-RC

4

+PF

-COM

-PF

6
7

5

REF

+RC

RV

2
3

1

FACTORY DEFAULT SETTING:

- FRONT PANEL VADJ CONTROL
- RELAY ALARM SELECTED
- VISUAL ALARM DISABLED
- REMOTE ON-OFF DISABLED
- DC ON PWR BY REF ENABLED

NOTE: NOT ALL COMPONENTS SHOWN.

DETAIL VIEW

SW1

SW2

SEE DETAIL VIEW

TAB