In-Situ RuggedCable for Level TROLL—Male connector end + stripped and tinned end User Manual
Short stripped & tinned cable, With male twist-lock connector, For level troll
Information Sheet
Catalog No. 0053310
SHORT STRIPPED & TINNED
CABLE
with Male Twist-Lock Connector
Desiccant
Dust cap—Remove
before use
Strain relief
Twist-Lock
connector
A
B
C
Dust cap
Vent tube
and
secured to
cable with
strap
Outboard
desiccant
attached to
cable vent
tube
(over)
A
B
C
Level
TROLL
®
Accessories
Connects a Level TROLL's RuggedCable
™
to a controller or logger for communication
via:
• Analog (4-20 mA)
•
RS485 Modbus
• SDI-12
•
RS232 Modbus (with a customer-supplied converter)
Male Twist-Lock connector mates with female Twist-Lock connector on the RuggedCable
Stripped & tinned wires on opposite end for wiring to PLC or logger
Removable, refillable outboard desiccant protects cable vent tube from condensation in
high-humidity environments
SPECIFICATIONS
Materials
PVC, titanium, nylon, Viton
®
Dimensions
13.33 cm (5.25 in) long, 19 mm (0.75 in) O.D.
Environmental Rating
IP67 when connected, not designed for submersion
Cable
0.9 m (3 ft) vented TPU (Thermoplastic Polyurethane)
Conductors
6 conductors, 24 AWG, polypropylene insulation
Desiccant pack
Clear acrylic, nylon, HDPE membrane
Desiccant
approx. 22 g silica gel, type 4
Max. recommended
SDI-12
61 m (200 ft)
cable lengths
Modbus 1259 m (4000 ft)
4-20 mA 1259 m (4000 ft)
CONNECTIONS
Refer to wiring diagrams on back of sheet. Trim back and insulate unused wires. The
shield should be wired to a chassis ground or earth ground.
Power Connections. The Red wire provides power for Modbus and SDI-12 modes.
The Brown wire provides power for the 4-20 mA mode. If power is present on the Brown
wire and not on the Red wire, the device enters the 4-20 mA mode automatically and
stays in the 4-20 mode until power is removed from the Brown wire or is applied to the
Red wire. The Red wire has priority — if power is applied to both wires at the same time,
the device will operate in Modbus or SDI-12 modes but not in 4-20.
Communications. The device automatically switches between Modbus and SDI-12
modes depending on which of the two interfaces has activity. Modbus and SDI-12
cannot be used at the same time — whichever one is currently in use will block commu-
nication on the other.
To communicate with the device using Win-Situ
®
5 software through a serial COM port:
Disconnect the RuggedCable from the short stripped and tinned cable connector. Attach
a TROLL Com to the RuggedCable. Connect the TROLL Com's DB9-pin connector to a
serial port on a PC running Win-Situ 5.
TIP: The desiccant may be removed
from the vent tube, if needed, for
better access to the conductor wires.
Pull the vent tube extender off the cable vent
tube to remove. After connecting and trimming
wires, attach desiccant vent tube to cable vent
tube and secure desiccant to cable with hook-
and-loop strap, as shown here.
for Level TROLL
®