Appendix A: Wire Requirements

Connecting external system accessories to the main circuits must be carefully considered to ensure
proper operation. It is important to use the correct type of wire, gauge and run length for each cir-
cuit. The following table lists NAC wiring requirements for the FCPS-24FS6 and FCPS-24FS8
Field Charger Power Supply.

NAC Load

(Amps)

Max.

allowable
total loop

resistance

(ohms)

CLASS-B

Max. allowable wire pair lenth

(feet)

CLASS-A

Max. allowable wire pair length

(feet)

AWG 12

solid

AWG 14

solid

AWG 16

solid

AWG 18

solid

AWG 12

solid

AWG 14

solid

AWG 16

solid

AWG 18

solid

0.25

6.00

1554

977

613

386

777

489

307

193

0.5

3.00

777

489

307

193

389

244

153

97

0.75

2.00

518

326

204

129

259

163

102

64

1.0

1.50

389

244

153

97

194

122

77

48

1.25

1.20

311

195

123

77

155

98

61

39

1.5

1.00

259

163

102

64

130

81

51

32

1.75

0.86

222

140

88

55

111

70

44

28

2.0

0.75

194

122

77

48

97

61

38

24

2.25

0.67

173

109

68

43

86

54

34

21

2.5

0.60

155

98

61

39

78

49

31

19

2.75

0.55

141

89

56

35

71

44

28

18

3.0

0.50

130

81

51

32

65

41

26

16

Table A.1 NAC Wiring Requirements for Power Supply

NOTE: Calculations are based on Direct-Current Resistance data for uncoated copper wire, per
National Electrical Code (2005 Edition) Table 8, Conductor Properties.

NOTE: These distances reflect the worst case scenario and are based on the correct draw of the
highest candela strobes at the low end of the supported NAC voltage with the entire load at the
end of the circuit. Further distances can be achieved by performing a point to point voltage
calculation that more accurately reflects the specific devices used and how they are dispersed on
the circuit.