Fire-Lite FCPS Series Field Charger/Power Supply User Manual
Page 40
![background image](/manuals/367195/40/background.png)
40
FCPS-24FS Series Instruction Manual — P/N 51883-L8:J1 8/30/13
Power Supply Requirements
Calculating the System Current Draw
Table 6.3 contains three columns for calculating current draws. For each column, calculate the cur-
rent and enter the total (in amperes) in the bottom row. When finished, copy the totals from Calcu-
lation Column 2 and Calculation Column 3 to Table 6.4 on page 41.
Device Type
Calculate Column 1
Primary, Non-Fire Alarm Current
(amps)
Calculate Column 2
Primary, Fire Alarm Current
(amps)
Calculation Column 3
Secondary, Non-Fire Alarm
Current
(amps)
Qty
X (current draw) = Total
Qty
X (current draw) =
Total
Qty
X (current draw) = Total
Main Circuit
Board
1
X [ 0.091] =
1
X [ 0.145] =
1
X [ 0.065] =
Power
Supervision Relay
[ ]
X [ 0.025] =
[ ]
X [0.025 ] =
[ ]
X [ 0.025] =
NAC/Output #1
[ ]
X [ ] =
NAC/Output #2
[ ]
X [ ] =
NAC/Output #3
[ ]
X [ ] =
NAC/Output #4
[ ]
X [ ] =
Current Draw
from TB4
Terminals 9 & 10
[ ] =
[ ] =
[ ] =
Sum each
column for totals
Primary Non-Alarm =
Primary Alarm =
Secondary Alarm =
Table 6.3 System Current Draw Calculations
- 2401B Circuit Board Standoff Placement (1 page)
- 411UDAC Fire Alarm Communicator (84 pages)
- 411UDAC Dig C Digital Communica unicatortor (1 page)
- 411UDAC Communicator Dress Panel (2 pages)
- 411UDAC Communicator Circuit Board & Transformer (2 pages)
- 411UDAC Fire Alarm Communicator Relay (1 page)
- ACC-25/50 Audio Command Center (1 page)
- ACC-25/50DA Distributed Audio Panel (84 pages)
- ACC-25/50ZS (1 page)
- ACM-16ATF Annunciator Modules (68 pages)
- ACM-8RF Control Relay Module (48 pages)
- APS-6RF Auxiliary Power Supply (28 pages)
- B524BI Plug-in Isolator (4 pages)
- B524RB(A) Plug-in Relay Detector Bases (4 pages)
- B310LP Plug-in Base for Addressable Detector (2 pages)
- B350LP Plug-In Base for Addressable Detector (4 pages)
- BB-55 Battery Box (1 page)
- BG-12 Series Manual Pull Stations (4 pages)
- BG-12LA Manual Pull Station (2 pages)
- BG-12LAO Manual Pull Station (2 pages)
- BG-12LO Manual Pull Station (2 pages)
- BG-12LPS Pre-Signal Manual Pull Station (2 pages)
- BG-12LR Agent Release Pull Station (2 pages)
- BG-12LX Addressable Pull Station (2 pages)
- BG-12SL Single Action Pull Station (2 pages)
- Central Station Receiver (1 page)
- CHG-120 Series Addendum - For Connection Of 100 Amp Hour Batteries (2 pages)
- CHG-120F Battery Charger (28 pages)
- CHG-75 Battery Charger (32 pages)
- CHS-6 Chassis (1 page)
- CHS-6 Chassis for BB-6 Cabinet (1 page)
- CMP-2401B Fire Alarm Control Panel (36 pages)
- CP355 Plug-in Addressable Ionization Sensor (2 pages)
- CRF-300 Relay Control Module (2 pages)
- DACT-UD2 Digital Alarm Communicator/Transmitter (52 pages)
- DP-4XF Dress Panel Kit PID (2 pages)
- ECC-50/100 Emergency Command Center (108 pages)
- ECC-50WBU Backup Amplifier (1 page)
- ECC-50DA/E Distributed Audio Amplifiers (26 pages)
- ECC-FFT (1 page)
- FCPS Series Field Software Change Procedure (2 pages)
- FHSC-RF FIREFIGHTERS HANDSET STORAGE BOX (1 page)
- ECC-FFT Firefighters Telephone (32 pages)
- H350 Addressable Thermal Sensor (2 pages)