Startup, Figure 2 interconnect wiring, 0 startup – Detcon 1600-N1P-RD User Manual
Page 7

1600/6400-N1P-RD
Serial Communications
Customer RS-485
A
Connections
RS-485
B
Customer Supplied Power
Ground
120VAC
2A
I
O
Black 18AWG
White 18AWG
Green
RV1
Purple 22AWG
White 22AWG
Input
S
B
A
J7
PCB
RS-485
Output
Black 18AWG
Red 18AWG
VDC IN
J4
+
-
J3
VR1
Pre-Wired
Customer Wired
Legend:
Power Supply
F1
P1
L1
J1
N
5
6
2
3
4
1
J2
+
+
8 7 6 5 4 3 2 1
S2
S1
S
J3
A
B
Re
d 18AWG
B
la
ck 18AWG
6400 Remote Display PCB
Figure 2 Interconnect Wiring
4.0 Startup
Before applying power, make sure that all wiring is terminated correctly.
NOTE: Applying power with devices hooked up incorrectly may cause damage.
Turn the AC Breaker switch to the ON position. Verify that the main touch-screen LCD comes up displaying
gas readings on the display. You should also verify that the Controller module is being polled by observing a
sequence of blinking LED’s on the backside of the remote display’s control module. Check to make sure these
display readings are identical to those at the Model 1600/6400 Controller.
1600/6400-N1P-RD- Instruction Manual Rev. 1.0
Page 3 of 14