7.0 Specifications

Input Power

9 VDC to 28VDC (For use in nominal 12VDC or 24VDC typical systems)

300mA Maximum (Including Sensor)

3W Maximum (Including Sensor)


Operating Temperature

–40°C to +70°C

Humidity: 10 to 95% Non-condensing

Range

Configurable:

From 1 to 25 in increments of 1

From 25 to 100 in increments of 5

From 100 to 1000 in increments of 50

From 1000 to 9999 in increments of 500

Accuracy/Repeatability

Sensor input current conversion to 10C Displayed reading: ±1%F.S. after trim procedure

Output current converted from 10C Displayed reading:

±1%F.S. after trim procedure

Inputs/Outputs

Communications: Serial RS-485 Modbus™

Input:

Analog 4-20mA DC, current sinking through 100 ohms.

Output:

Analog 4-20mA DC, current sourcing.

Open-Collector outputs follow relay coils.

Relays

Relay Contact terminations: Common, Normally Open, and Normally Closed (x 3 Relays)

Relay Contact Manufacturer’s Specification:
Resistive load: 5A, 250VAC; 5A, 30 VDC
Inductive load: 2A, 250VAC; 2A, 30 VDC
Max. Operating current: 5A

Alarm/Fault Alarm Timing and Triggering

Alarms are inhibited during the power-up initialization period indicated by the display “Warm Up”.
Alarm signal delay: nominally 2 seconds
Alarm set-point hysteresis: nominally 1 unit
Alarm minimum activity before acknowledge silences it: 10 seconds.

Warranty

One

year

Five year fixed fee service policy

10C Control Module Instruction Manual Rev. 0.B