beautypg.com

Field wiring, Figure 7 typical installation, Table 2 wire gauge vs. distance – Detcon TP-524D-HRT User Manual

Page 12: Figure 7, 6 field wiring, Detcon model tp-524d-hrt solid-state h

background image

Model TP-524D-HRT

TP-524D-HRT Instruction Manual

Rev. 0.3

Page 8 of 48

Drain

Conduit

"T"

EYS Seal Fitting

PGM

1

PGM

2

MODEL

TP-524D

HOUSTON, TEXAS

FLT

1

2

CAL

MicroSafe

H2S Gas Sensor

ALM ALM

TM

Figure 7 Typical Installation

NOTE: Any unused ports should be blocked with suitable ¾” male NPT plugs.

Detcon

supplies one ¾” NPT male plug with each J-box enclosure. If connections are other than ¾”
NPT, use an appropriate male plug of like construction material.

2.6 Field Wiring

Detcon Model TP-524D-HRT solid-state H

2

S sensor assemblies require three conductor connections between

power supplies and host electronic controller’s 4-20mA / HART Interface. Wiring designations are DC+, DC-
, MA (sensor signal). A 250 ohm load resistor is needed on the 4-20 mA line when it is not being used. The
maximum wire length between sensor and 24VDC source is shown in the Table below. The maximum wire
size for termination in the Junction Box is 14 AWG.

Table 2 Wire Gauge vs. Distance

AWG

Wire Dia.

Meters

Feet

Over-Current

Protection

22

0.723mm

700

2080

3A

20

0.812mm

1120

3350

5A

18

1.024mm

1750

5250

7A

16

1.291mm

2800

8400

10A

14

1.628mm

4480

13,440

20A

NOTE 1: Wiring table is based on stranded tinned copper wire and is designed to serve as a
reference only.

NOTE 2: Shielded cable is required for installations where cable trays or conduit runs include
high voltage lines or other possible sources of induced interference. Separate conduit runs are
highly recommended in these cases.