B-5

OPERATION

B-5

RANGER 200

Welding

Output Range

Setting

0

50

100

150

210

Permissibl Power Watts

(Unity Power Factor)

6000

4500

3000

1500

0

Permissible

Current in

@120 VAC *

40*

38*

25

12.5

0

Auxiliary
Amps

@ 240 VAC

25

18.8

12.5

6.3

0

* Each duplex receptacle is limited to 20 amps.
** Not to exceed 25 A per 120 VAC branch circuit when splitting the 240 VAC output.

Ranger 200 Simultaneous Welding and Power Loads

Ranger 200 Extension Cord Length Recommendations

(Use the shortest length extension cord possible sized per the following table.)

Current

(Amps)

15

20
15
20
25

Voltag
eVolts

120
120
240
240
240

Load

(Watts)

1800
2400
3600
4800
6000

30

60

(9)

(18)

40
30
75
60

(12)

(9)

(23)
(18)

75
50

150
100

90

(23)
(15)
(46)
(30)
(27)

125

88

225
175
150

(38)
(27)
(69)
(53)
(46)

175
138
350
275
225

(53)
(42)

(107)

(84)
(69)

300
225
600
450
250

(91)
(69)

(183)
(137)

(76)

Maximum Allowable Cord Length in ft. (m) for Conductor Size

Conductor size is based on manimum 2.0% voltage drop.

14 AWG

12 AWG

10 AWG

8 AWG

6 AWG

4 AWG

Simultaneous Welding and Auxiliary Power
Loads

The previous auxiliary power ratings are with no weld-
ing load. Simultaneous welding and power loads are
specified in the following table. The permissible cur-
rents shown assume that current is being drawn from
either the 120 VAC or 240 VAC supply (not both at the
same time).