Operation – Lincoln Electric IM660 RANGER 200 User Manual
Page 20
![background image](/manuals/363615/20/background.png)
B-5
OPERATION
B-5
RANGER 200
Welding
Output Range
Setting
0
50
100
150
210
Permissibl Power Watts
(Unity Power Factor)
6000
4500
3000
1500
0
Permissible
Current in
@120 VAC *
40*
38*
25
12.5
0
Auxiliary
Amps
@ 240 VAC
25
18.8
12.5
6.3
0
* Each duplex receptacle is limited to 20 amps.
** Not to exceed 25 A per 120 VAC branch circuit when splitting the 240 VAC output.
Ranger 200 Simultaneous Welding and Power Loads
Ranger 200 Extension Cord Length Recommendations
(Use the shortest length extension cord possible sized per the following table.)
Current
(Amps)
15
20
15
20
25
Voltag
eVolts
120
120
240
240
240
Load
(Watts)
1800
2400
3600
4800
6000
30
60
(9)
(18)
40
30
75
60
(12)
(9)
(23)
(18)
75
50
150
100
90
(23)
(15)
(46)
(30)
(27)
125
88
225
175
150
(38)
(27)
(69)
(53)
(46)
175
138
350
275
225
(53)
(42)
(107)
(84)
(69)
300
225
600
450
250
(91)
(69)
(183)
(137)
(76)
Maximum Allowable Cord Length in ft. (m) for Conductor Size
Conductor size is based on manimum 2.0% voltage drop.
14 AWG
12 AWG
10 AWG
8 AWG
6 AWG
4 AWG
Simultaneous Welding and Auxiliary Power
Loads
The previous auxiliary power ratings are with no weld-
ing load. Simultaneous welding and power loads are
specified in the following table. The permissible cur-
rents shown assume that current is being drawn from
either the 120 VAC or 240 VAC supply (not both at the
same time).