beautypg.com

3 operating instructions – Condec PIN7010 User Manual

Page 8

background image

4

PIN7000/PIN7010 Operation and Maintenance Manual

Figure 2-1. Initial Setup/Operating

NOTE: PIN7000 shown, AC Input (1), Test Port (9) and Input Port (4) are on back side of PIN7010 Rack Mountable
Intensifier.

2.3

Operating Instructions

NOTE: See Figure 2-1, when following these steps.

1. Optional External Cylinder: Open the cylinder valve (5) by rotating counter-clockwise slowly until it

stops.

Other: Open the, customer supplied, pressure source valve.

2. Using the REGULATOR (10), adjust the maximum intensifier pump input pressure, as read by the

REGULATED PRESSURE gauge (6), to 1/10 of the target value. The unit utilizes an internal intensifier
with a 10:1 ratio. As an example, setting regulated pressure to 300 PSI would generate an output pressure
of 3,000 PSI. Using this technique, the device to be pressurized, is fully protected from being
accidentally over-pressurized.

3. To generate pressure, enable the

POWER

switch (2) and monitor the pressure as it builds in the

ACCUMULATOR PRESSURE gauge (7). Turn the

POWER

switch (2) off when 10% more than the

target pressure has been achieved.

NOTE: The intensifier POWER switch (2) can be operated in two modes. The up position is continuous and the down
position is momentary/jog.

4. To apply pressure, the

VENT

valve (12) must be closed. Open the

PRESSURE

valve (11), slowly

counter-clockwise, while monitoring the

OUTPUT PRESSURE

gauge (8), until reaching the target value.

5. Use either the

PRESSURE

(11) or

VENT

valve (8) to obtain a specific pressure reading. Both provide

precise control. As the pressure approaches the desired value, the valve being used for control should be
rotated slowly clockwise to its closed position.

NOTE: Use the intensifier POWER switch (2) if the ACCUMULATOR PRESSURE gauge (7) reading falls below required
target pressure value.

This manual is related to the following products: