APPENDIX A - EXAMPLES

A-2

.

EXAMPLE 2 (Trip Band )

Require an alarm to be activated when the pressure falls out of an acceptance band of 25

PSI to 50 PSI. The trip points must be able to be entered from the front panel in the “run” mode.
Assume the base mode set for PSI. To eliminate output noise set the hysteresis for 0.1 PSI .
Require a front panel status display to indicate when the pressure is acceptable or high or low.
For failsafe it is required that the alarm will sound if the indicator losses power.

In the TRIP PT menu set the following:

TRIP POINT SELECT MENU

PARAMETER

CHOICES

DESCRIPTION

TRIP

ON

Trip Option enabled

DISPLAY

ACCEPT

Applies to trip band 1 only.

RECALL

MODIFY

Can view and modify trip point status from front panel .

TRIP 1

ON

Trip 1 is enabled.

TYPE

BAND

Trip Band mode. High and low trip entry.

TRIP 1

UNDER

Sets polarity of trip band 1 output to be active when in
band .

TRIP1.H

+ 50.00

Trip band 1 upper value

TRIP1.L

+ 25.00

Trip band 1 lower value

HYST1.H

DESCEND

Hysteresis upper trip band 1 applies to descending data.

HYST1.H

+ 0.10

Hysteresis upper trip band 1 value

.

HYST1.L

ASCEND

Hysteresis lower trip band 1 applies to ascending data.

HYST1.L

+ 0.10

Hysteresis lower trip band 1 value.

TRIP 2

OFF

Trip 2 is disabled.

Connect output as follows:

RELAY OPTION BOARD
OUT 1 N.C.

TB3-1 -----------------

Alarm 1

--+V

OUT 1 COM

TB3-3 -----------------

Ret

Results:
By using N.C. Connection the Alarm will sound if Indicator losses power.

When the pressure is between 25 and 50 PSI the display will say “ACCEPT” and the output
alarm will be inactive.

When the pressure is over 50 PSI, the display will prompt with “HIGH” and the output alarm
will be active. The alarm will be inactive when the pressure falls below 49.9 PSI.