APPENDIX A - EXAMPLES

A-1

.

EXAMPLE 1(Dual Trip Point )

Require an alarm to be activated when the pressure exceeds 50 PSI and a second alarm to

be activated when the pressure exceeds 75 PSI. The trip points must be able to be entered from
the front panel in the “run” mode. Assume the base mode set for PSI. To eliminate output noise
set the hysteresis for 0.1 PSI when descending.

In the TRIP PT menu set the following:

TRIP POINT SELECT MENU

PARAMETER

CHOICES

DESCRIPTION

TRIP

ON

Trip Option enabled

DISPLAY

TRIP

Display indication for trip point as TRIP x when output
active.

RECALL

MODIFY

Can view and modify trip point status from front panel.

TRIP 1

ON

Trip 1 is enabled.

TYPE 1

TRIP PT

Trip Point mode. High trip entry only.

TRIP 1

OVER

Sets polarity of trip point 1output to be active over (above)
trip point.

TRIP1.H

+ 50.00

Trip Point 1 value set for 50 PSI

HYST1.H

DESCEND

Hysteresis upper trip point 1 applies to descending data.

HYST1.H

+ 0.10

Hysteresis upper trip point 1 value of 0.01 PSI.

TRIP 2

ON

Trip 2 is enabled.

TYPE 2

TRIP PT

Trip Point mode. High trip entry only.

TRIP 2

OVER

Sets polarity of trip point 2 output to be active over
(above) trip point.

TRIP2.H

+ 75.00

Trip point 2 value set for 75 PSI

HYST2.H

DESCEND

Hysteresis upper trip point 2 applies to descending data.

HYST2.H

+ 0.10

Hysteresis upper trip poiint 2 value set for 0.10 PSI.

Connect output as follows:

RELAY OPTION BOARD
OUT 1 N.O.

TB3-2 -----------------

Alarm 1

--+V

OUT 1 COM

TB3-3 -----------------

Ret

OUT 2 N.O.

TB3-5 -----------------

Alarm2

--+V

OUT 2 COM

TB3-6 -----------------

Ret

Results:
Alarm 1 will be active when pressure is above 50 PSI and will deactivate when the
pressure goes below 49.90 PSI.
Alarm 2 will be active when pressure is above 75 PSI and will deactivate when the
pressure goes below 74.90 PSI.