Schematic diagrams, Low voltage circuit high voltage circuit – STI HK3 User Manual
Page 7
![background image](/manuals/361277/7/background.png)
7
Schematic Diagrams
2 AMP CIRCUIT
BRE
AKER
OVERTEMP SAFETY
1
2
4
3
5
6
CONTROL
110 OR 240 VAC
SINGLE PHASE
1
2
4
3
5
6
FAN
PWR
+
_
FAN
LOW TEMP WARNING
(16-33VDC 600mA)
LOW VOLTAGE CIRCUIT
HIGH VOLTAGE CIRCUIT
TERMINAL
BLOCK
TERMINAL
BLOCK
CHASSIS
HEATER
E
CLOSE @ 40
˚
F (4
˚
C)
OPEN @ 65
˚
F (18
˚
C)
OPEN @ 120
˚
F (40
˚
C)
CLOSE @ 80
˚
F (27
˚
C)
OPEN @ 50
˚
F (10
˚
C)
CLOSE @ 32
˚
F (0
˚
C)
24VDC (±10%), 90mA
FROM MONITOR MODULE
TO TEMP WARNING
FROM MONITOR MODULE
TO MANUAL STATIONS
EARTH GROUND
MANUAL STATIONS
110 OR 240 VAC
50/60 Hz
100 WATTS
This manual is related to the following products: