OptiLogic Series
OL2408 Analog Voltage Input Module
Inputs
8
Power required
700mA
Input Type
0-5 VDC or
0-10VDC
Conversion Type
Successive approximation
Resolution
14 bit (1 in 16384)
Full Scale Calibration
Error
+/- 15 counts max.
+/- 5 counts typical
Input Impedance
10 MOhm
Offset Calibration error
+/- 2 counts max.
Maximum Voltage
Input
+/- 15VDC
Max. Terminal wire
gauge
18 AWG (use copper
conductors)
Linearity error
+/- 1.25 count max
Terminal Strip
Plug In (removable)
Input stability
+/- 2 counts
Terminal Screws
Slotted (0.1
” blade max.)
Terminal block
torque
2.2 lb-in
Required Temperature
rating of field installed
conductors
60
C/75C
Type
17
Subtype
1
1
2
4
5
6
7
8
9
10
3
L
O
2408
Analog
Voltage
Input
10
9
8
7
6
5
4
3
2
1
0-5 VDC
or 0-10 VDC
0-5 VDC
or 0-10 VDC
0-5 VDC
or 0-10 VDC
0-5 VDC
or 0-10 VDC
0-5 VDC
or 0-10 VDC
0-5 VDC
or 0-10 VDC
0-5 VDC
or 0-10 VDC
0-5 VDC
or 0-10 VDC
Terminal
Terminal
1
Common
6
Channel 4
2
Common
7
Channel 5
3
Channel 1
8
Channel 6
4
Channel 2
9
Channel 7
5
Channel 3
10
Channel 8
The OL2408 comes set up for 0-5VDC input range. If you need 0-10VDC input range, you must remove the plastic
module cover by lifting the board latches over the retainer hooks on the PC board. Then, place the jumper on both
pins of J2 and replace the plastic module cover. To change back to 0-5VDC range, repeat the process and remove
the jumper. Having the cover over the range selector jumper ensures that it will not be inadvertantly changed.