beautypg.com

Ol2208 dc digital input module, Optimation, inc, Opti logic series – Nematron OptiLogic Series User Manual

Page 20: Connection diagram

background image

Optimation, Inc.

(256)883-3050

20

www.optimate.com

OptiLogic Series

OL2208 DC Digital Input Module

Inputs

8

Card Cage Power
required

60mA

Input Type

DC Optocoupled

Status Indicators

Logic side LED

Voltage Range

10 - 30 VDC

Input Impedance

2.7K

Min. On Current (per
point)

3.3 mA

Max. On Current (per
point)

11 mA

Commons

2

Terminal Strip

Plug In (removable)

Max. Terminal wire
gauge

18 AWG (use copper
conductors)

Terminal screw

Slotted (0.1

” blade

max.)

Required Temperature
rating of field installed
conductors

60

C/75C

Weight

1.2 oz (34g)

Terminal block torque

2.2 lb-oz

Type

1

Subtype

1

10

10

9

9

8

8

7

7

6

6

5

5

4

4

3

3

2

2

1

1

10-30VDC

Sourcing

Sinking

10-30VDC

IN7

IN7

IN6

IN6

IN5

IN5

IN4

IN4

IN3

IN3

IN2

IN2

IN1

IN1

IN0

IN0

Connection diagram

The OL2208 DC Digital Input module can be used in either sourcing or
sinking application (all 8 inputs must be used in the same manner). Each
input is optocoupled to provide system isolation. Individual LED
indicators provide a visual feedback of current status.

module internal

circuit

optical

isolation

To

OptiLogic

processor

Terminal

Terminal

1

Common

6

In 3

2

Common

7

In 4

3

In 0

8

In 5

4

In 1

9

In 6

5

In 2

10

In 7

1

2

4

5

6

7

8

9

10

3

0
2

3

1

4

5

6

7

L

O

O

2208

I

N