beautypg.com

Ol2252 dual high speed pulse counter – Nematron OptiLogic Series User Manual

Page 22

background image

Optimation, Inc.

(256)883-3050

22

www.optimate.com

OptiLogic Series

OL2252 Dual High Speed Pulse Counter

Inputs (all)

8

Card Cage Power
Required

100 mA

Pulse Inputs

2

Status Indicators

Logic side LED

Input Voltage

10 - 30 VDC

Input Impedance

2.7K ohms

Input frequency (on
pulse inputs)

15 KHz maximum

Commons

2

Min. On Current (per
point)

3.3 mA

Terminal Strip

Plug In (removable)

Max. On Current (per
point)

11 mA

Terminal Screws

Slotted (0.1

” blade

max.)

Max terminal wire
gauge

18 AWG

Required Temperature
rating

of field installed

conductors

60

C/75C

Weight

1.2 oz (34g)

Terminal block torque

2.2 lb-in

Type

80

Subtype

1

Terminal

Terminal

1

Common

6

Reset 2

2

Common

7

Enable 1

3

Pulse 1

8

Enable 2

4

Pulse 2

9

In 6

5

Reset 1

10

In 7

The OL2252 module provides two independent high speed pulse counter inputs. Each input counter will accurately
count pulse inputs up to 15KHz. Inputs may be sourcing or sinking type There are a number of operating options
available with the OL2252. The six remaining inputs can be used as predefined control signals or as general
purpose inputs. These options are detailed in the following pages.

module internal

circuit

optical

isolation

To

OptiLogic

processor

1

2

4

5

6

7

8

9

10

3

0

2

3

1

4

5

6

7

L

O

O

2252

P

U

L

S

E

I

N

10

9

8

7

6

5

4

3

2

1

10-30VDC

IN7
IN6

RESET 1

RESET 2

EN 2
EN 1

Pulse 2
Pulse 1