Ol2304 four channel voltage output – Nematron OptiLogic Series User Manual
Page 28
Optimation, Inc.
(256)883-3050
28
OptiLogic Series
OL2304 Four Channel Voltage Output
Outputs
4
Card Cage Power
required
700mA
Output Ranges
0-5V, 0-10V, +/-5V, +/-10V
(individual channel
configurable)
External Power
required
none
Resolution
12 bit (1 in 4096)
Output current
+/-5mA
Output type
Single ended, 1
common
Short circuit current
+/-15mA
Offset calibration
error
+/-8 counts @ +/-10V
+/-16 counts @ +/-5V
+/-16 counts @ 0-10V
+/- 32 counts @ 0-5V
Max terminal wire
gauge
18 AWG (use copper
conductors)
Nonlinearity
+/- 1 count
Terminal strip
Plug In (removable)
Load impedence
2Kohm mimimum
Terminal screws
Slotted (0.1
” blade
max)
Terminal block torque
2.2 lb-in
Required Temperature
rating of field installed
conductors
60
C/75C
Type
25
Subtype
1
The OL2304 analog output module is range configurable, on a channel by channel basis, to any of four common
output ranges. Each channel can be configured, via software for either 0-5V, 0-10V, +/-5V or +/-10V ranges. The
module generates its own isolated output power supply, eliminating any need for an outside source.
Terminal
Terminal
1
Common
5
Common
2
Out 1
6
Out 3
3
Common
7
Common
4
Out 2
8
Out 4
8
7
6
5
4
3
2
1
Channel 4
Channel 3
Channel 2
Channel 1
+
+
+
+
-
-
-
-