2 pump location - twin pump – Stuart Turner Monsoon U1.5 bar Twin User Manual

Page 6

background image

- 6 -

2.26

Non-preferred pump location: If it is not possible to locate the pump in the

preferred area due to site limitations and it is necessary to position the unit

in the loft, or in a position above the secondary tapping that feeds the pump,

then there is an increased risk of air locks. This risk must be eliminated.

The following measures are suggestions that may overcome the problem:

A “U” bend or downward loop in the supply pipe to the pump of 350 mm depth

before rising to the pump should ensure the cylinder vents its air up the

expansion pipe not up the pump feed (Fig. 3).

Table 1

Model

Max.

inlet

head

Max.

outlet

head

U1.5

8 m

8 m

U2.0

U3.0

U4.0

12 m

12 m

U4.5

2 PUMP LOCATION - TWIN PUMP

Fig. 3

Max. inlet head (see table 1)

Min. inlet head

0.5

m

hot water
services

least preferred area

200

mm

min

350

mm

Max. outlet head

(see table 1)

Negative head

Fig. 4

Max. static inlet pressure see table 1