Error Messages durng Acquston
Code
Descrpton
Cause/Correctve Actons
W[631]
Data Lack
Data was unexpectedly lost. Reduce the number of acquired data points or
connected instruments, or lengthen the scan interval.
E[673]
Cannot open communication
Communication failed to open
Check whether the power to the connected measuring instruments with which
you wish to open communications is ON, and whether the cables are connected
correctly. Also check the following.
• For Ethernet
Is the address correct, is the TCP/IP protocol installed in Windows, and is the
Ethernet card installed correctly?
• For RS-232 and RS-422A
Are the baud rate, port numbers (COM1–COM9), and addresses (RS422)
correct? Is the PC serial port valid? Is the cable type correct?
E[674]
Communication error
Communication Errors
Same as E[673].
E[675]
Communication time out
Communication timeout
Same as E[673].
W[880]
Do not specify communication
port
Specify the communication parameters.
W[881]
Current connecting recorder
configuration is mismatch!
The recorder is:
Change the parameters for the main unit.
W[882]
Cannot login recorder
Recorder login error
W[882]
Cannot Get recorder
information
Failed to get settings from the recorder. Check whether the communication status
and connected instruments matches those specified in the software. If they do not
match, perform automatic model determination again.