Logging In, Logging Out, and Signing
2-7
IM 04L41B01-01E
1
2
3
Index
App
• Signature > Sign from recorder
Set the signature privilege range for DX key operations.
Setting
Description
Off
You cannot sign files from the DX.
Sign1
You can sign files from the DX using the Signature1 privileges.
Sign1+2
You can sign files from the DX using the Signature1 and Signature2 privileges.
Sign1+2+3
You can sign files from the DX using the Signature1, Signature2, and
Signature3 privileges.
• Signature > Signature at batch stop
You can configure this setting so that a screen for making a signature (historical trend
display) appears when recording stops (memory stop).
Setting
Description
On
The historical trend display appears automatically at memory stop.
Off
The display does not change at memory stop.
Note
You cannot set Signature at batch stop when:
• Sign from recorder is set to Off.
Even when Signature at batch stop is set to On, the historical trend display will not appear
when:
• The process type is Batch, and the measured data is divided into multiple files.
• A user without signature privileges performs memory stop.
• The multi batch function (/BT2 option) is being used, and batch overview mode is enabled.
• Signature > FTP transfer at signing
You can transfer measured data files (display or event data files) to an FTP server
after you sign them. You need to configure the FTP client settings so that display and
event data is transferred.
Setting
Description
On
Measured display and event data files are only transferred to an FTP server
after they are signed. Also, the Transfer wait time settings are invalid; transfer
is executed immediately.
Off
Measured data files are not transferred to an FTP server after they are signed.
For information about FTP client settings, see the Communication Manual.
Procedure
• Changing Login Settings during Recording (Memory sampling)
You can change login settings during recording (memory sampling). For operating
instructions, see the explanation later in this section.
• The setting change operation can only be performed by an administrator.
• The user privilege settings cannot be changed.
• The settings of a user who is logged in cannot be changed.
Note
• If you switch to Basic Setting mode while recording (memory sampling) is in progress,
actions of the Event Action function are ignored as long as you remain in Basic Setting
mode. Events occurring while in Basic Setting mode are ignored. The only exception are
snapshots which can still be taken with the USER key.
• If you register or change the registration of a Web mode user while recording (memory
sampling) is in progress, you must turn the power to the DX OFF then back ON again for the
changes to take effect.
2.1 Registering Users and Setting the Signature Method