Yokogawa Button Operated DX2000 User Manual
Page 4
3
2. LOG
Input
Specifications
2.1. Converting the LOG Input (Relationship between the Input Voltage and Digital
Display)
Trend display (logarithmic scale): Displays the input voltage on a logarithmic
scale.
Digital display:
Displays the result obtained by converting the
input voltage using the equation below.
¾
The relationship between the input voltage of special LOG range and digital
display value is shown below.
Input voltage
X
Lower limit of display span VL
Upper limit of display span
VU
Scale lower limit
SL
Scale upper limit
SU
VL Input
X
VU
T
U
1.0E
SL
Y
1.0E
SU
Digital display value Y = 10
(SU-SL)*(X-VL)/(VU-VL)+SL
This manual is related to the following products: