beautypg.com

B-2-2, Field diagnostic online setting display, B-2-2 field diagnostic online setting display – Yokogawa FieldMate User Manual

Page 9: Quick configuration

background image

B-3

IM 01R01A15-01EN

2nd Edition : 2013.11.07-00

B-2-2 Field Diagnostic Online Setting Display

Start up the Field Diagnostic Online Setting function from the menu of FieldMate. Select

Field Diagnostic Online Setting in the menu of Additional Functions (See Figure A-4-1).

The Field Diagnostic Online Setting Display appears. Follow the procedure below.

■ Quick Configuration

1.

Click the Quick Configuration button. The Quick Configuration [Online Setting]

Display appears.

2.

Follow the procedure below to categorize or recategorize each alarm into any of the

four statuses.

• Drag & drop: Any alarm can be moved among five alarm statuses including “Not

Assigned

” (e.g. from “Failure” to “Check Function”).

• Mask ON/OFF: Check or clear the box to turn masking on or off.
• Right-click menu: “Copy,” “Paste,” “Remove,” “Mask On,” or “Mask Off” can be

set.

Colored title: Click any of the color

ed titles to show the Alarm Map and Alarm

Mask setting display.

Figure B-2-2 Quick Configuration Display