beautypg.com

Appendix b ne 107 parameters for f, Oundation, Fieldbus ............ app – Yokogawa FieldMate User Manual

Page 21

background image

App.-2

IM 01R01A15-01EN

2nd Edition : 2013.11.07-00

Appendix B NE 107 Parameters for

FOUNDATION fieldbus

The added NAMUR NE 107 parameters for FOUNDATION fieldbus devices and item

names used in this software are shown below.

Table Appendix B-2

Parameters (NE 107)

Details

Item Name

FD_FAIL_ALM
FD_CHECK_ALM
FD_MAINT_ALM
FD_OFFSPEC_ALM

Indicate alarms which should notify Host

Alarm Broadcast

FD_FAIL_MASK
FD_CHECK_MASK
FD_MAINT_MASK
FD_OFFSPEC_MASK

Set alarms which should notify Host

Alarm Mask

FD_FAIL_ACTIVE
FD_CHECK_ACTIVE
FD_MAINT_ACTIVE
FD_OFFSPEC_ACTIVE

Indicate aggregated devices alarms

Alarm Indication

FD_FAIL_MAP
FD_CHECK_MAP
FD_MAINT_MAP
FD_OFFSPEC_MAP

Set NE 107 classification of aggregated devices
alarms

Alarm Map

FD_FAIL_PRI
FD_CHECK_PRI
FD_MAINT_PRI
FD_OFFSPEC_PRI

Set priority whether should notify Host

Alarm Priority

FD_EXTENDED_ACTIVE_n

Indicate all device alarms related to NE 107

Detailed Field
Diagnostics Alert

FD_EXTENDED_MAP_n

Set NE 107 classification of all device alarms related
to NE 107

Escalation Enable

FD_RECOMMEN_ACT

Indicates an alarm and action which the user should
do

Recommended
Action

FD_SIMULATE

Enable/Disable simulation of NE 107

Simulation

FD_VER

Version information of this specification

FD_VER