B-1-1, Field diagnostics (ne 107) on f, Oundation – Yokogawa FieldMate User Manual
Page 7: Fieldbus devices
B-1
IM 01R01A15-01EN
2nd Edition : 2013.11.07-00
B
Field Diagnostics on FOUNDATION
Fieldbus Devices
B-1
Outline
B-1-1 Field Diagnostics (NE 107) on
FOUNDATION Fieldbus Devices
NAMUR NE 107 is a standard for self-diagnosing field devices. It yields reliable results,
categorizes alarms into four standardized statuses and outputs corresponding signals,
allows users to configure diagnostics, and provides detailed information for experts.
To perform and confirm the settings of transmitters in accordance with NE 107 more
easily, FieldMate incorporates a field diagnostics function, Field Diagnostics.
Figure B-1-1 shows the flow of alarm information and corresponding displays which are
specified as field diagnostics (NE 107) on FOUNDATION Fieldbus devices.
Figure B-1-1 Flow of alarm information and corresponding displays
I
ndividual alarms, which have been
specified based on vendors and devices.
Alarms to be sent to any of aggregated
field diagnostic alarms can be selected or
deselected. This can be set in the
Extended Configuration Display.
Selected alarms are included in any of 32
aggregated field diagnostic alarms. (See
Appendix A “Aggregated Field Diagnostic
Alarms for FOUNDATION fieldbus”)
Alarm diagnostic configuration, results
mapping and masking can be enabled/
disabled for each aggregated field
diagnostic alarm. These settings can be
checked, set, and changed in the Quick
Configuration Display and Detailed
Configuration Display.
Quick
Config.
Display
Detailed
Config.
Display
Extended
Config.
Display
NA
NA
NA
NA
NA
NA
NA
NA
Available
NA
NA
NA
NA
Available
The setting can be changed in
Results are output as one of four
standardized status signals.
Simulation
is possible
Available
Available
Available
Available