Appendix A Aggregated Field Diagnostic
Alarms for FOUNDATION Fieldbus
Table Appendix A-1 describes all of the 32 Aggregated Field Diagnostic Alarms used for
Yokogawa products.
Table Appendix A-1 Aggregated Field Diagnostic Alarms (32-bit)
Alarm bit
Initial alarm
category
Label
Description
31
F
Electronics failure
An electric/electronic failure such as amplifier breakdown may have
occurred.
30
F
Sensor/Actuator failure
A sensor/actuator failure may have occurred.
29
F
Potential failure
A device failure may have occurred, or abnormal settings, dirt, poor contact
of wiring and connectors, or poor board installation may have occurred.
28
F
(Device specific failure alarm)
Device-specific failure
27
F
(Device specific failure alarm)
Device-specific failure
26
F
Backup function in operation
A breakdown has occurred in at least one system of redundant sensors.
The backup sensor is operating normally.
25
-
(Reserved)
(Reserved)
24
C
Firmware update error
A firmware update error has occurred. The operation is being covered by
the existing firmware.
23
C
Communication configuration error
Communication setting is improper.
22
C
Non-operating-state
Non-routine operations such as initialization, calibration, testing, or
maintenance are in progress.
21
C
Calibration warning
The device is running with existing settings or abnormal calibration values
because the calibration was performed during an alarm condition.
20
C
Device configuration error
The settings of sensors or actuators are improper.
19
C
Function restricted
The device is running partially.
18
C
Simulation mode
The device is running in the simulation mode.
17
C
Manual mode
The device is running in the manual mode.
16
C
Function Block notice
A function block is in the “O/S” or “Unscheduled” state.
15
C
(Device specific function check
Device-specific function check alarm
14
-
(Reserved)
(Reserved)
13
S
Sensor/Actuator out of range
The measured value of the sensor or the operating point of the actuator is
out of range.
12
S
Out of operating limit
The environment or operating condition is out of the specification.
11
S
(Device specific out of specification
alarm)
Device-specific out-of-spec alarm
10
-
(Reserved)
(Reserved)
9
M
Temporal decrease of value quality
Although the accuracy satisfies the specification, the measured values are
temporarily unreliable due to degradation.
8
M
Deterioration estimated by Time
Based Maintenance
The operation time or the number of operations has exceeded the limit.
7
M
Deterioration estimated by Condition
Based Maintenance
The internal algorithm has detected an abnormality.
6
M
(Device specific maintenance
request alarm)
Device-specific “maintenance request” alarm
5
M
(Device specific maintenance
request alarm)
Device-specific “maintenance request” alarm
4
-
(Reserved)
(Reserved)
3
C
Optional function configuration error
A setting of sub-functions is abnormal although it will not affect the main
measuring functions. Masking this alarm does not affect the operation of
the main functions.
2
-
Alarm related information
Supplementary information is displayed.
1
-
Process alarm
A process alarm has occurred. This alarm may be caused by an
abnormality of devices or peripheral devices.
0
-
CHECK
CHECK