Appendix A Aggregated Field Diagnostic

Alarms for FOUNDATION Fieldbus

Table Appendix A-1 describes all of the 32 Aggregated Field Diagnostic Alarms used for

Yokogawa products.

Table Appendix A-1 Aggregated Field Diagnostic Alarms (32-bit)

Alarm bit

Initial alarm

category

Label

Description

31

F

Electronics failure

An electric/electronic failure such as amplifier breakdown may have
occurred.

30

F

Sensor/Actuator failure

A sensor/actuator failure may have occurred.

29

F

Potential failure

A device failure may have occurred, or abnormal settings, dirt, poor contact
of wiring and connectors, or poor board installation may have occurred.

28

F

(Device specific failure alarm)

Device-specific failure

27

F

(Device specific failure alarm)

Device-specific failure

26

F

Backup function in operation

A breakdown has occurred in at least one system of redundant sensors.
The backup sensor is operating normally.

25

-

(Reserved)

(Reserved)

24

C

Firmware update error

A firmware update error has occurred. The operation is being covered by
the existing firmware.

23

C

Communication configuration error

Communication setting is improper.

22

C

Non-operating-state

Non-routine operations such as initialization, calibration, testing, or
maintenance are in progress.

21

C

Calibration warning

The device is running with existing settings or abnormal calibration values
because the calibration was performed during an alarm condition.

20

C

Device configuration error

The settings of sensors or actuators are improper.

19

C

Function restricted

The device is running partially.

18

C

Simulation mode

The device is running in the simulation mode.

17

C

Manual mode

The device is running in the manual mode.

16

C

Function Block notice

A function block is in the “O/S” or “Unscheduled” state.

15

C

(Device specific function check

Device-specific function check alarm

14

-

(Reserved)

(Reserved)

13

S

Sensor/Actuator out of range

The measured value of the sensor or the operating point of the actuator is
out of range.

12

S

Out of operating limit

The environment or operating condition is out of the specification.

11

S

(Device specific out of specification
alarm)

Device-specific out-of-spec alarm

10

-

(Reserved)

(Reserved)

9

M

Temporal decrease of value quality

Although the accuracy satisfies the specification, the measured values are
temporarily unreliable due to degradation.

8

M

Deterioration estimated by Time
Based Maintenance

The operation time or the number of operations has exceeded the limit.

7

M

Deterioration estimated by Condition
Based Maintenance

The internal algorithm has detected an abnormality.

6

M

(Device specific maintenance
request alarm)

Device-specific “maintenance request” alarm

5

M

(Device specific maintenance
request alarm)

Device-specific “maintenance request” alarm

4

-

(Reserved)

(Reserved)

3

C

Optional function configuration error

A setting of sub-functions is abnormal although it will not affect the main
measuring functions. Masking this alarm does not affect the operation of
the main functions.

2

-

Alarm related information

Supplementary information is displayed.

1

-

Process alarm

A process alarm has occurred. This alarm may be caused by an
abnormality of devices or peripheral devices.

0

-

CHECK