■ Detail Configuration
1.
Click the Detail Configuration button. The Detail Configuration Display appears.
2.
For each setting (Alarm Map, Alarm Indication, Alarm Mask, and Alarm Broadcast)
of the aggregated field diagnostic alarms, set the alarm status (Failure, Check
Function, Out of Specification, Maintenance Required).
• The background of alarms with the setting changed becomes magenta. Click the
“Apply Field Diagnostic Setting to Device” button at the bottom right to fix the change.
The background returns to the original color.
When testing alarm processing with the Simulation function
1.
Click the Simulation Switch button.
2.
Enter the parameter for disabling simulation in the SIM_ENABLE_MSG (REMOTE
LOOP TEST SWITCH for EJX and EJA-E), and then click the OK button.
3.
Checking the box below Simulate displays checkboxes corresponding to each of
the aggregated field diagnostic alarms.
• The background of alarms with the setting changed becomes magenta. Click the
“Apply Field Diagnostic Setting to Device” button at the bottom right to fix the change.
The background returns to the original color.
When configuring Alarm Priority functions
1. Alarm priority can be set for each alarm status (range: 0 to 15).
When Alarm Priority of alarm status is set to
“0” or “1”, alarms are not broadcasted
and Alarm Broadcast display will be changed to inapplicable status. (
“⃠” mark will
be displayed under the Alarm Broadcast title)
Figure B-2-3 Detail Configuration Display
Checking this box enables
the checkboxes below.
Alarm priority levels
can be set.
“
⃠” mark is appeared when Alarm
priority is set to “0” or “1”.
When Alarm Priority is set
into “0” or “1”, alarm is
not generated.