beautypg.com

3 setting parameters using the bt200, 1 parameter summary, Setting parameters using the bt200 -4 – Yokogawa EJA530A User Manual

Page 35: Parameter summary -4

background image

IM 01C21F01-01E

8-4

8. BRAIN TERMINAL BT200 OPERATION

8.3 Setting Parameters Using the BT200

8.3.1 Parameter Summary

Instruments to which applicable:
F: Differential pressure transmitters

EJA110A, EJA120A, and EJA130A

P: Pressure transmitters

EJA310A, EJA430A, EJA440A, EJA510A, and EJA530A

L: Liquid level transmitters

EJA210A and EJA220A

No.

Description

Model+capsule type

Tag number

Applica-

bility

P L

F

01

02

T0805.EPS

Rewrita-

bility

16 alphanumerics

GOOD/ERROR

Remarks

Item

MODEL

TAG NO.

Self-diagnostic result

03

SELF CHECK

Measured data display

A

–5 to 110%*

3

Menu name

DISPLAY

Output (in %)

A10 OUTPUT (%)

–19999 to 19999

Output (in engineering
units)

A11 ENGR.

OUTPUT

Unit specified in D30

Amplifier temperature

A20 AMP TEMP

Unit specified in D30

Capsule temperature

A21 CAPSULE

TEMP

Sensor type

B

16 uppercase alphanumerics

Menu name

SENSOR
TYPE

Model+span

B10 MODEL

Style number

B11 STYLE NO.

–32000 to 32000

Lower range-limit

B20 LRL

–32000 to 32000

Upper range-limit

B21 URL

–32000 to 32000

Minimum span

B30 MIN SPAN

Unit specified in D31*

1

Static pressure

A30 STATIC

PRESS

–32000 to 32000

Input (indicated as the
value after zeroing)

A40 INPUT

GOOD/ERROR, CAP MODULE FAULT, AMP MODULE FAULT,
OUT OF RANGE, OUT OF SP RANGE*

1

, OVER TEMP (CAP),

OVER TEMP (AMP), OVER OUTPUT, OVER DISPLAY,
ILLEGAL LRV, ILLEGAL HRV, ILLEGAL SPAN, and
ZERO ADJ OVER

Self-diagnostic
messages

A60 SELF CHECK

Maximum static
pressure*

6

B40

Same as A60

MAX STAT.P.

Self-diagnostic
messages

B60 SELF CHECK

Setting data

C

16 alphanumerics

Menu name

SETTING

Tag number

C10 TAG. NO.

Selected from mmH

2

O, mmAq,

mmWG, mmHg, Torr, Pa, hPa, kPa,
MPa, mbar, bar, gf/cm

2

, kgf/cm

2

,

inH

2

O, inHg, ftH

2

O, psi, or atm

Measurement range
units

C20 PRESS UNIT

–32000 to 32000(but within
measurement range)

Measurement range,
lower range value

C21 LOW RANGE

Self-diagnostic
messages

C60

Same as A60

SELF CHECK

–32000 to 32000(but within
measurement range)

Measurement range,
higher range value

C22 HIGH

RANGE

Selected from 0.2*

2

, 0.5, 1.0, 2.0,

4.0, 8.0, 16.0, 32.0, or 64.0 sec.

Damping time constant

C30 AMP

DAMPING

Selected from OUT:LIN; DSP:LIN,
OUT:LIN; DSP:SQR,
OUT:SQR; DSP:SQR

Output mode and
integral indicator mode

C40 OUTPUT

MODE

0.0 to 20.0%
LINEAR/ZERO

Low cut

D10 LOW CUT

Low cut mode

D11 LOW CUT

MODE

NORMAL %/USER SET,
USER & %/INP PRES, PRES & %

Display selection

D20 DISP SELECT

Auxiliary setting data 1

D

Menu name

AUX SET 1

Default Value

As specified when ordered.
As specified when ordered.

As specified when ordered.

As specified when ordered.

2.0 s

As specified when ordered.
If not specified,
OUT: LIN; DSP: LIN.

8 uppercase
alphanumerics

Engineering unit for
display

D21 DISP UNIT

10.0%
LINEAR

–5.0 to 110.0%

Lower output range-limit

D15 OUT LIMIT(L)

–5.0%*

1

–5.0 to 110.0%

Upper output range-limit

D16 OUT LIMIT(H)

110.0%

–19999 to 19999

Engineering range,
lower range value

D22 DISP LRV

–19999 to 19999

Engineering range,
higher range value

D23 DISP HRV

As specified when ordered.

As specified when ordered.

As specified when ordered.

deg C/deg F

Temperature setting
units

D30 TEMP UNIT

deg C

*1: Unless otherwise specified by order. When optional code /F1 is specified, substitute the value –5 with –2.5.