IM 01C21F01-01E

4-2

4. INSTALLATION

IMPORTANT

Tighten the hexagonal nut part of the capsule
assembly. See Figure 4.2.3.

F0404.EPS

Capsule assembly

Figure 4.2.3 Tightening Transmitter

4.3 Rotating Transmitter Section

The DPharp transmitter section can be rotated in 90

°

segments.

1) Remove the two Allen screws that fasten the

transmitter section and capsule assembly, using the
Allen wrench. Also, remove the pipe for the model
EJA530A with Measurement span code A, B, and
C, using the slotted screwdriver.

2) Rotate the transmitter section slowly in 90

° seg-

ments.

3) Tighten the two Allen screws to a torque of 5 N·m,

and replace the pipe if applied.

IMPORTANT

Do not rotate the transmitter section more than
180

°.

F0403.EPS

Rotate 90

° or 180° segments

Transmitter section

Capsule assembly

Conduit connection

Zero-adjustment screw

Pipe

Gasket

Allen screw

Figure 4.3 Rotating Transmitter Section

4.4 Changing the Direction of

Integral Indicator

IMPORTANT

Always turn OFF power, release pressure and
remove a transmitter to non-hazardous area
before disassembling and reassmbling an
indicator.

An integral indicator can be installed in the following
three directions. Follow the instructions in section 9.4
for removing and attaching the integral indicator.

F0405.EPS

Figure 4.4 Integral Indicator Direction