Appendix

42

WATLOW Series 945 User's Manual

Specifications

Secondary Output (Heat, Cool or None)
• Solid state relay, Form A, 0.5A @ 24VAC min., 264VAC
maximum, opto-isolated, zero cross switching. Off state
impedance is 20K

minimum for 945A-XBXX-X000

units, and 31M

for 945A-XKXX-X000 units.

• Electromechanical relay, Form A, 6A @ 120/240VAC, 6A
@ 28VDC, 1/8 hp. @ 120VAC, 125VA @ 120VAC. Off
state impedance is 20K

min. Typical relay life is

100,000 cycles.
• Switched DC (Open collector), 500

min. load resis-

tance, 1K

load, 9mA min., 22mA max., non-isolated.

Alarms
• Electromechanical relay, Form A (N.O.) or B (N.C.), 6A
@ 120/240VAC, 6A

@ 28VDC, 1/8 hp. @ 120VAC,

125VA @ 120VAC. Off state impedance is 20K

min.

Typical relay life is 100,000 cycles.
• Latching or non-latching.
• Process or deviation.
• Separate high and low values.
• Alarm silencing (inhibit) on power up for Alarm 1.

Retransmit Output
• 4-20mA into a 600

maximum load, non-isolated.

• 0-5VDC into a 10K

minimum load, non-isolated.

• Retransmit of process or set point. User selectable range.

Accuracy
• Calibration Accuracy & Sensor Conformity:

±

0.1% of

span,

±

1LSD, 77

°

F

±

5

°

F(25

°

C

±

3

°

C) ambient & rated

line voltage

±

10%.

• Accuracy Span: 1000

°

F or 540

°

C minimum.

• Temperature Stability: 0.1

°

F/

°

F (0.1

°

C/

°

C) change in

ambient.
• Voltage Stability:

±

0.01% of span / % of rated line

voltage.

Communications
• Serial data communications.
• RS-422A or RS-423A (RS-232C compatible) or EIA-485.
• ANSI X3.28 protocol, or XON/XOFF protocol.
• Isolated.
• Data logging.
• #6 compression type screw terminals.

Agency Approvals
• UL recognized, File #E43684, UL873.
• CSA recognized, File # LR30586.

Terminals
• #6 compression type screw terminals.

Power
• 120/240VAC +10%, -15%, 50/60Hz,

±

5%.

• 16VA maximum.
• Data retention upon power failure via nonvolatile
memory.

Operating Environment
• 32 to 149

°

F/0 to 65

°

C.

• 0 to 90% RH, non-condensing.

Dimensions
• Height:

3.8 in

97 mm

• Width:

3.8 in

97 mm

• Overall depth:

7.0 in

178 mm

• Behind panel depth:

6.0 in

153 mm

• Weight:

2.5 lb max.

0.4 kg

Control Mode
• Single or dual set point, non-ramping.
• Single input, dual outputs, dual alarms.
• Optional retransmit of set point or process variable.
• Control outputs: User selectable as: Heat, Heat/Heat,

Heat/Cool, Cool, Cool/Cool, Cool/Heat.
• Outputs independent, or related via deadband for

Heat/Cool.

• ON/OFF: Determined by the HYSX parameter for

Outputs 1 and 2.

• Proportional band: 0 to 999

°

F/0 to 555

°

C/0 to 999 U

or 0 to 999.9% of span.
Reset: 0.00 to 9.99 repeats per minute.
Integral: 0 and 00.1 to 99.9 minutes per repeat.
Rate/Derivative: 0.00 to 9.99 minutes.
Cycle time: 1 to 60 seconds.

• Dead band:

±

99

°

F,

±

99 units or

±

55

°

C (

±

9.9

°

F,

±

9.9

units or

±

5.5

°

C for rtd.1 and process units)

Operator Interface
• Membrane front panel.
• Dual, four digit 0.56" (14 mm) LED displays.
• MODE, AUTO/MANUAL, UP, and DOWN keys.

Input
• Automatic cold junction compensation for thermocouple.
• RTD input 2 or 3 wire, platinum, 100 ohm @ 0

°

C

software selectable, JIS curve #3916 (0.003916

/

/

°

C)

or DIN curve #3850(0.003850

/

/

°

C).

• Sensor break protection de-energizes control outputs to

protect system or selectable bumpless transfer to
manual operation.

• Grounded or ungrounded sensors.

°

F,

°

C, or process variable units are user selectable.

• Operating ranges user selectable.

J t/c:

32 to

1382

°

F or

0 to

750

°

C

K t/c:

-328 to

2282

°

F or

-200 to 1250

°

C

T t/c:

-328 to

662

°

F or -200 to

350

°

C

N t/c:

32 to

2282

°

F or

0 to 1250

°

C

C t/c:

797 to

4200

°

F or

425 to 2315

°

C

PT 2 (Platinel 2) 32 to

2543

°

F or

0 to 1395

°

C

R t/c:

32 to

2642

°

F or

0 to 1450

°

C

S t/c:

32 to

2642

°

F or

0 to 1450

°

C

B t/c:

1598 to

3092

°

F or

870 to 1700

°

C

1

°

RTD:

-328 to

1112

°

F or

-200 to 600

°

C

0.1

°

RTD:

-99.9 to

392.0

°

F or -99.9 to 200.0

°

C

0-5VDC:

-500 to 3500 units

4-20mA:

-500 to 3500 units

Primary Output (Heating or Cooling)
• Solid state relay, 0.5A @ 24VAC min., 264VAC max.

opto-isolated, zero cross switching. Off state impedance
is 20K

min. for 952A-XBXX-X000 units, and 31M

for 945A-XKXX-X000 units.

• Electromechanical relay, Form C, 6A @ 120/240VAC, 6A

@ 28VDC, 1/8 hp. @ 120VAC, 125VA @ 120VAC. Off
state impedance is 20K

minimum. Typical relay life of

100,000 cycles.

• Switched DC (Open collector), 500

min. load resis

tance, 1K

load,9mA min., 22mA max., non-isolated.

• 4-20mA reverse or direct acting into a 600

maximum

load impedance,non-isolated.

• 0-5 VDC reverse or direct into a 1K

minimum load

impedance, non-isolated.