beautypg.com

Wiring guide, Checking for ground loops, Noise suppression devices available from watlow – Watlow Series 945, 1/4 DIN Microprocessor-BasedAuto-tuning Control User Manual

Page 30

background image

WATLOW Series 945 User's Manual

Appendix

30

Wiring Guide

• "Islatrols" and other similar power line filters are designed to carry the power for

the control circuit and "buffer" the control circuit from A.C. line noise. Devices
like the Islatrol use media (electromagnetic filtering) other than electric circuits to
filter out electrical noise. Take care in matching the power capabilities of the filter
with power demands of the circuit. Keep line filters as close to the control as
possible to minimize the area for interference pick up.

• Islatrols are available from:

Control Concepts Corporation
328 Water Street
P.O. Box 1380
Binghamton, NY 13902-1380
Phone: 607/724-2484

I - 101 (1A, 120VAC)

I - 105 (5A, 120VAC)

I - 115 (15A, 120VAC)

I - 202 (2.5A, 208/240VAC)

I - 207 (7.5A, 208/240VAC)

• The ultimate protection is an "uninterruptable" power supply. This "senses" the

A.C. power line; when the line fluctuates, a battery powered 60Hz inverted circuit
takes over, supplying power within one-half to one cycle of the A.C. line; very
expensive.

Checking for Ground Loops

To check for ground loops, disconnect the ground wire at the ground termination.
Measure the resistance from the wire to the point where it was connected. The
ohmmeter should read a high ohm value. If you have a low ohm value across this
gap, there is at least one ground loop present in your system.

Or check for continuity; your reading should be "open." If you do find continuity,
begin looking for the ground loops. Begin disconnecting ground in the system one
at a time, checking for continuity after each disconnection. When continuity reads
"open" you have eliminated the ground loop(s). Also, as you reconnect grounds,
keep making the continuity test. It is possible to reconnect a ground loop.

Noise Suppression Devices Available From Watlow

Watlow Controls stocks a few key noise suppression parts. You may order these
by calling your local Watlow distributor.

Table 4 -
Noise Suppression
Device Ratings

Item

Electrical Ratings

Part Number

Common Mode Line Filter

250V, 3 Amp

0804-0196-0000

Differential Mode Line Filter

Refer to the Islatrol listing above.

Metal Oxide Varistor

150V, 80 Joule

0802-0273-0000

MOV

130V, 38 Joule

0802-0304-0000

MOV

275V, 75 Joule

0802-0266-0000

MOV

275V, 140 Joule

0802-0405-0000

Quencharc

0.01µf, 100 , 600VAC

0804-0147-0000