Watlow Series 935A User Manual

Page 60

background image

5 8

Watlow Series 935A User’s Manual

PID Menu

Prompt

Range

Default

Hidden if *

Your Settings

[`tA9] = [P```]

0°F or 0°C

[-999] [9999]

[-9(9] [99(9]

Select a value,
adjustable between

-999° and 9999°F or C
or -99.9° and 999.9°F or
C to eliminate a
difference between the
displayed temperature
and the actual
temperature.

[`CAL]

Calibration Offset

[`tA9] = [P```];

or if

[Pb`h] = 0;

or if

[Pb`h] is hidden; and
if [Pb`c] = 0;

or if

[Pb`c] is hidden

0 minutes

[`)00] [`(99]

Select a value,
adjustable between 0.00
and 9.99 minutes.

[``dE]

Derivative Function

[`tA9] = [P```];

or if

[Pb`h] = 0;

or if

[Pb`h] is hidden; and
if [Pb`c] = 0;

or if

[Pb`c] is hidden

5.00 minutes/repeat

[``)0] [9(99]

Select a value,
adjustable between 0.0
and 99.99
minutes/repeat.

[``It]

Integral Function

[`tA9] = [P```];

or if

[Pb`c] = 0

or if

[Pb`c] is hidden

5.0 seconds

[``)1] [`6)0]

[``%0] [`6)0]

Select a value between
0.1 and 60.0 seconds
(Solid-State Relay or
Switched DC) or 5.0 and
60.0 seconds
(Electromechanical
Relay).

[Ct`c]

Cycle Time Cool